Scope of Work/Materials
13850 (28 31 00) - 3
Bid No.041818-Installation of New Fire Alarm System at Adams Elementary School
2.
Local Piezo-Electric Signal in Control Panel: Sound at a pulse rate.
3.
80-Character LCD Display: Indicate all information associated with fire alarm condition,
including type of alarm point and its location within protected premises.
4.
Historical Log: Record information associated with fire alarm control panel condition,
along with time and date of occurrence.
5.
System output programs assigned via control-by-event equations to be activated by
particular point in alarm shall be executed, and the associated system outputs (alarm
notification appliances and/or relays) shall be activated.
6. Strobes flash synchronized continuously.
7.
Audible devices sound continuous Temporal pattern until system is reset.
E.
Fire Alarm System Functionality
: Owner Provided
1.
Install a complete, electrically supervised distributed, Style 7 networked
analog/addressable fire alarm and control system, with analog initiating devices.
2.
Fire Alarm System:
a.
Incorporate E3 Series multiprocessor-based control panels, with Intelligent Loop
Interface ILI-MB-E3 and RPT-E3 repeater modules communicating over peer-to-peer
token ring network with capacity of up to 64 nodes.
3.
Each ILI-MB-E3 SLC module: Incorporate 2 Signaling Line Circuits (SLC), with capacity to
support up to 159 analog addressable detectors and 159 addressable modules per SLC.
4.
All data transmits over single pair of wires or fiber optic cable.
5.
Each Network Node: Incorporate Boolean control-by-event programming, including as a
minimum AND, OR, NOT, and Timer functions.
6.
Control Panels: Capability to accept firmware upgrades via connection with laptop
computer, without requirement of replacing microchips.
7.
Network:
a.
Based on peer-to-peer token ring technology operating at 625 K baud, using Style 7
configuration.
b.
Capability of using twisted-pair wiring, pair of fiber optic cable strands up to 200
microns, or both, to maximize flexibility in system configuration.
8.
Each Network Node:
a.
Capability of being programmed off-line using Windows-based software utilized by
fire alarm system manufacturer. Capability of being downloaded by connecting
laptop computer into any other node in system. Systems that require system
software to be downloaded to each transponder at each transponder location shall
not be acceptable.
b.
Capability of being grouped with any number of additional nodes to produce a
“Region”, allowing that group of nodes to act as 1, while retaining peer-to-peer
functionality. Systems utilizing
“Master/Slave” configurations shall not be
acceptable.
c.
C
apability of annunciating all events within its “Region” or annunciating all events
from entire network, on front panel LCD without additional equipment.
9.
Each SLC Network Node: Capability of having integral DACT (digital alarm communicator
transmitter) that can report events in either its region, or entire network to single central
station monitoring account.
10. Each Control Panel: Capability of storing its entire program and allow installer to activate
only devices that are installed during construction, without further downloading of system.
12. Password Protection: Each system shall be provided with 4 levels of password protection
with up to 16 passwords.