On the
CEM Circuit Expander Module
of a
Flex 8
...
Function
DIP Switch
Switch “Off”
Switch “On”
Indicating Circuit #3
Audible Device (Bell) Only
Switch 6, #1
Silenceable
Non-Silenceable
Indicating Circuit #4
Audible or Visual Device
Switch 6, #2
Silenceable
Non-Silenceable
Switch 6, #3
Audible Device (Bell)
Visual Device (Strobe)
Not Used
Switch 6, #4
-----------------
-----------------
Initiating Circuit #5
Alarm Only
Switch 5, #1
Normal Alarm
Verified Alarm
Initiating Circuit #6
Alarm Only
Switch 5, #2
Normal Alarm
Verified Alarm
Initiating Circuit #7
Alarm or Waterflow
Switch 5, #3
Normal
Verified Alarm / Retarded Waterflow
Switch 5, #4
Alarm
Waterflow
Initiating Circuit #8
Alarm or Supervisory
Switch 5, #5
Normal
Verified Alarm (no effect on Supv.)
Switch 5, #6
Alarm
Supervisory
Switch 5, #7
Non-Latching Supervisory
(No effect on Alarm)
Latching Supervisory
(No effect on Alarm)
Not Used
Switch 5, #8
-----------------
-----------------
Notes:
&
AFTER ANY CONFIGURATION SWITCHES ARE CHANGED, IT IS NECESSARY TO PERFORM A SYSTEM RESET !!
&
Only Indicating Circuit 4 may be configured for Visual Devices.
&
If Initiating Circuit 7 is configured as Waterflow, the corresponding Verified selection becomes a Retard
selection.
Note: Do not use Retard Operation with any external Retarding device; maximum Retard may not exceed 120
seconds.
&
If Initiating Circuit 8 is configured as Alarm, the corresponding Latching selection has no effect.
&
If Initiating Circuit 8 is configured as Supervisory, the corresponding Verified selection has no effect.
&
The selection of Class A/B (Style Z/Y) Indicating Circuits is only a matter of how they are wired. No Programming
is necessary See Connection Information.(
Figures 9 & 10
).
&
If Class A (Style D) Initiating Circuits are selected the appropriate Board Jumpers must also be set.
Class B Initiating Circuits 5&6 combine to create Class A Circuit #3, and Class B Initiating Circuits 7&8 combine
to create Class A Circuit #4. In Class A operation, DIP Switches for Circuits 5 to 8 are ignored, and LED
Indicators for Circuits 5 to 8 are non-functional
.