2-3. Slim duct type
Model name
ARYG18LLTB
Power supply
1Ø 230 V ~50 Hz
Available voltage range
198—264 V
Fan
Airflow rate
Cooling
HIGH
m
3
/h
940
MED
880
LOW
820
QUIET
750
Heating
HIGH
940
MED
880
LOW
820
QUIET
750
Type × Q'ty
Sirocco fan × 3
Motor output
W
81
Recommended static pressure
Pa
0 to 90
Sound pressure level *
Cooling
HIGH
dB (A)
32
MED
31
LOW
30
QUIET
29
Heating
HIGH
33
MED
32
LOW
31
QUIET
29
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 700 × 39.9
Fin pitch
mm
1.30
Rows × Stages
3 × 14
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Steel sheet
Color
—
Dimensions
(H × W × D)
Net
mm
198 × 900 × 620
Gross
274 × 1,168 × 772
Weight
Net
kg
23
Gross
27
Connection
pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Gas
Ø12.70 (Ø1/2)
Method
Flare
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Drain hose
Material
Hard PVC
Size
mm
Ø 25 (I.D.), Ø 32 (O.D.)
Remote controller type
Wired (Wireless [option])
NOTES:
• Values mentioned in the table are based on the following conditions:
– Static pressure: 25 Pa
• The protective function might work when using it outside the operation range.
• *: Sound pressure level:
– These are the measured values in the manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 5 -
2-3. Slim duct type
2. Specifications
INDOOR UNITS
SIMULTANEOUS
MULTI
INDOOR UNITS
SIMULTANEOUS
MULTI
Содержание AUYG18LVLB
Страница 151: ...Part 2 OUTDOOR UNIT SIMULTANEOUS MULTI AOYG72LRLA AOYG90LRLA ...
Страница 181: ...Part 3 SYSTEM DESIGN ...
Страница 333: ...Part 4 OPTIONAL PARTS ...