9-3. Pump down
WARNING
• Never touch electrical components such as the terminal blocks except the button on the display
board. It may cause a serious accident such as electric shock.
• During the pump-down operation, make sure that the compressor is turned off before you re-
move the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2-way or g. 3-way
valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage
and even injury.
CAUTION
• Perform the pump down operation before disconnecting any refrigerant pipe or electric cable.
• Collect refrigerant from the service port or the 3-way valve if pump down cannot be performed.
• In case of a group control system installation, do not turn the power off until pump down is com-
pleted in all outdoor units.
(Group control system installation described in “SPECIAL INSTALLATION METHODS” in the in-
stallation manual of the indoor unit.)
¢
Pump down procedure
Confirm that the power is off, and then open the service panel.
Symbols in the following table indicate LED status.
"○": Lights off, "●": Lights on
1. Check the 3-way valves (both the liquid side and gas side) are opened.
2. Turn the power on.
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
●
○
○
○
○
○
○
○
3. Press [PUMP DOWN] button for 3 seconds or more after 3 minutes after power on.
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
●
○
●
○
○
●
●
●
LED display lights on as shown in the above figure, and the fans and the compressor start op-
erating.
NOTE:
If the [PUMP DOWN] button is pressed during compressor operation, the compres-
sor will stop, and the operation will start after about 3 min.
4. LED display will change as shown below about 3 minutes after the compressor starts. Fully
close the 3-way valve on the liquid pipe side at this stage.
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
●
○
●
○
○
○
●
●
NOTE:
If the valve on the liquid pipe side is not closed, the pump down cannot be per-
formed.
- 297 -
9-3. Pump down
9. Check and test
SYSTEM
DESIGN
SYSTEM
DESIGN
Содержание AUYG18LVLB
Страница 151: ...Part 2 OUTDOOR UNIT SIMULTANEOUS MULTI AOYG72LRLA AOYG90LRLA ...
Страница 181: ...Part 3 SYSTEM DESIGN ...
Страница 333: ...Part 4 OPTIONAL PARTS ...