1. Specifications
Type
Inverter heat pump
Model name
AOYG72LRLA
AOYG90LRLA
Power supply
3N 400 V ~ 50 Hz
Available voltage range
342—456 V
Starting current
A
11.5
14.1
Capacity
Cooling
Rated
kW
19.00
22.00
Btu/h
64,800
75,000
Min.—Max.
kW
8.40—20.90
10.30—24.20
Btu/h
28,600—71,300
35,100—82,500
Heating
Rated
kW
22.40
27.00
Btu/h
76,400
92,100
Min.—Max.
kW
7.20—24.60
8.50—29.70
Btu/h
24,500—83,900
29,000—101,300
Input power
Cooling
Rated
kW
5.99
7.24
Heating
6.12
7.65
Current
Cooling
Rated
A
11.2
13.5
Max.
15.8
20.6
Heating
Rated
11.5
14.1
Max.
15.8
20.6
Power factor
Cooling
Rated
%
77.2
77.4
Heating
76.8
78.3
Fan
Airflow rate
Cooling
m
3
/h
8,400
8,400
Heating
8,400
9,000
Type × Q'ty
Propeller × 2
Motor output
W
111 × 2
Sound pressure level *1
Cooling
dB (A)
55
55
Heating
55
57
Sound power level
Cooling
dB (A)
68
68
Heating
70
71
Heat exchanger type
Dimensions (H × W
× D)
mm
1,386 × 1,293 × 36.38
Main: 1,386 × 1,293 × 36.38
Sub: 1,386 × 773 × 18.19
Fin pitch
1.45
Rows × Stages
2 × 66
2.6 × 66
Pipe type
Copper
Fin
Type (Material)
Corrugate (Aluminum)
Surface treatment
Blue fin
Compressor
Type × Q'ty
Scroll × 1
Motor output
W
4,700
Refrigerant
Type
R410A
Factory charge
g
5,600
7,100
Refrigerant oil
Type
FVC68D
Amount
cm
3
2,300
Enclosure
Material
Painted galvanized steel
Color
Beige
Approximate color of MUNSELL 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
1,428 × 1,080 × 480
Gross
1,557 × 1,174 × 600
Weight
Net
kg
163
172
Gross
181
190
Connection pipe
Size
Liquid
mm (in)
Ø 12.70 (Ø 1/2)
Gas
Ø 25.40 (Ø 1)
Method
Brazing
Pre-charge length
m
30
Max. length
100
Max. height difference
30
Operation range
Cooling
°C
-15 to 46
Heating
-20 to 24
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 144 -
1. Specifications
OUTDOOR UNIT
AOYG72-90LRLA
OUTDOOR UNIT
AOYG72-90LRLA
Содержание AUYG18LVLB
Страница 151: ...Part 2 OUTDOOR UNIT SIMULTANEOUS MULTI AOYG72LRLA AOYG90LRLA ...
Страница 181: ...Part 3 SYSTEM DESIGN ...
Страница 333: ...Part 4 OPTIONAL PARTS ...