3) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
Setting value
Setting description
Factory setting
11
00
Standard
01
Long interval
02
Short interval
03
No indication
♦
Intervals will differ depending on the indoor unit type as follows.
Setting
description
Compact
cassette
Cassette
Slim duct
Duct
Floor
Floor/Ceiling
Standard
2,500 hours
400 hours
Long interval
4,400 hours
1,000 hours
Short interval
1,250 hours
200 hours
4) Ceiling height
Select the appropriate ceiling height according to the place of installation.
Function number
Setting value
Setting description
Factory setting
20
00
Standard (2.5 m to 3.0 m)
♦
01
High ceiling (3.0 m or more)
02
Low ceiling (2.7 m)
For the specific height for each setting value, refer to “Installation space” in Chapter 3.
In case of cassette type models:
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet
mode.
5) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number
Setting value
Setting description
Factory setting
21
00
Normal
♦
01
High static pressure 1
02
High static pressure 2
03
High static pressure 3
6) Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
Function number
Setting value
Setting description
Factory setting
22
00
4-way
♦
01
3-way
- 286 -
8-6. Function details
8. Function settings
SYSTEM
DESIGN
SYSTEM
DESIGN