2. Pipe design
2-1. Important items when using refrigerant (R410A)
•
Refrigerant piping material and wall thickness
It is necessary to use seamless copper tubes for refrigerant use. Thickness of tubes are shown in
table below.
Nominal diameter
in
1/4
3/8
1/2
5/8
3/4
7/8
1-1/8
Outside diameter
mm
6.35
9.52
12.70
15.88
19.05
22.22
28.58
Material
JIS H3300 C1220T-O or equivalent*
1
JIS H3300 C1220T-H
or equivalent*
2
Wall thickness*
3
mm
0.8
1.0
1.2
1.0
*1: Allowable tensile stress ≥ 33 N/mm
2
*2: Allowable tensile stress ≥ 61 N/mm
2
*3: Endurance pressure of the pipes: 4.2 MPa
Select the pipe size in accordance with local rules.
•
Lubricant
Refrigerant
R410A (Mixed refrigerant)
Lubricant
Synthetic oil
•
Tools
R410A work requires a number of special tools. Since the tools (with * symbol) for R22 work can-
not be used for R410A, prepare them beforehand.
Tool name
Process and application
Pipe cutter
Pipe cutting
Refrigerant piping work
Flaring tool*
Pipe flaring work
Torque wrench*
Flare nut connection
Expander
Expansion at pipe connection
Pipe bender
Pipe bending work
Nitrogen gas
Pipe interior oxidation prevention
Air tightness test
Welder
Pipe brazing
Gauge manifold*
Vacuum evacuation and
refrigerant charging operation
check
Air tightness test ~ Refrigerant
additional charging
Charging hose*
Vacuum pump (with adapter)*
Vacuum drying
Electronic scale for refrigerant
charging
Refrigerant additional charging
Gas leak tester*
Gas leakage test
*: For details, refer to the service manual.
- 179 -
2-1. Important items when using refrigerant (R410A)
2. Pipe design
SYSTEM
DESIGN
SYSTEM
DESIGN