7-8. Drain pump control
¢
Drain control for cooling operation
During the compressor in operation
•
Triggering condition
The thermostat is turned on during cooling or dry mode.
•
Operation details
The drain pump is turned on.
•
Release condition
– The thermostat is turned off.
When the compressor is not in operation
" for the operation after release.
– The compressor is stopped.
When the compressor is not in operation
" for the operation after release.
– The operation is switched to heating mode.
When the compressor is not in operation
" for the operation after release.
– The float switch is turned on.
" for the operation after release.
– The compressor is stopped by Anti-freezing control.
The compressor is stopped by Anti-freezing control
lease.
When the compressor is not in operation
•
Triggering condition
– The thermostat is turned off.
– The compressor is stopped.
– The operation is switched to heating mode.
– The float switch is turned off.
•
Operation details
– Count 180 minutes.
– Start drain pump intermittent operaion.
On
Off
Drain pump
3 min
3 min
3 min
Trigger point
(0 min)
3 min
10 min
60 min
180 min
•
Release condition
– 3 minutes drain pump operation is finished after 180 minutes count.
– The operation is switched to cooling or dry mode.
During the compressor in operation
" for the operation after release.
– The float switch is turned on.
" for the operation after release.
•
Operation after release
The drain pump is turned off and the air conditioner operate according the settings.
7-8. Drain pump control
- (04-29) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG36KRLB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Страница 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Страница 50: ......
Страница 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Страница 120: ......
Страница 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...