3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢
Fan speed
Indoor fan speed is defined as below.
Operation mode
Fan mode
Speed (rpm)
AUXG36KRLB
AUXG45KRLB
AUXG54KRLB
Heating
HIGH
640
670
690
MED+
600
630
680
MED
560
590
630
LOW
510
530
570
QUIET
430
470
480
Cool air prevention
300
300
300
S-LOW
270
270
270
Cooling/Fan
HIGH
640
670
690
MED
560
590
630
LOW
510
530
570
QUIET
430
470
480
Soft quiet
300*
1
300*
1
300*
1
S-LOW
270*
2
270*
2
270*
2
Dry
X zone: 430
J zone: 430
X zone: 470
J zone: 470
X zone: 480
J zone: 480
*1: Fan mode only
*2: Cooling mode only
¢
Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH while indoor unit fan
only runs.
When fan mode is set at AUTO, it operates on MED fan speed.
¢
Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Cooling: Auto)
When room
temperature rises
When room
temperature drops
Tr - Ts ≥ 2
°C
HIGH mode
MED mode
LOW mode
2
°C
> Tr - Ts ≥ 1
°C
1
°C > Tr - Ts
Tr - Ts ≥ 2.5
°C
2.5
°C
> Tr - Ts ≥ 1.5
°C
1.5
°C > Tr - Ts
3-1. Indoor fan control
- (04-12) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG36KRLB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Страница 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Страница 50: ......
Страница 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Страница 120: ......
Страница 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...