2-23. E: 73. Heat exchanger (Middle/Outlet) temperature
thermistor error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 73
Detective actuator
Heat exchanger liquid temperature
thermistor
•
Heat exchanger liquid temperature thermistor short
or open detected
•
Heat exchanger middle temperature thermistor
short or open detected
Heat exchanger middle
temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check Point 1 : Check the connector connection and cable open
•
Connector connection state check
•
Cable open check
↓
Check Point 2 : Check the thermistor
•
For the outdoor unit heat exchanger thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-24.
If the voltage does not appear, replace main PCB.
↓
End
2-23. E: 73. Heat exchanger (Middle/Outlet) temperature thermistor error (Outdoor
unit)
- (03-28) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AUXG36KRLB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Страница 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Страница 50: ......
Страница 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Страница 120: ......
Страница 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...