1-3. Dry operation
The compressor rotation frequency shall change according to the temperature, set temperature, and
room temperature variation which the room temperature sensor of the indoor unit has detected as
shown in the table below.
Zone is defined by set temperature and room temperature.
•
Compressor frequency range
Unit: rps
Model name
Outdoor temperature zone
Operating frequency
AUXG36KRLB
X zone
32
J zone
32
Y zone
0
AUXG45KRLB
X zone
40
J zone
40
Y zone
0
AUXG54KRLB
X zone
33
J zone
33
Y zone
0
•
Compressor control based on room temperature
Ts+0.5°C
Ts -1.5
°C
Ts-0.5
°C
Ts+1.5
°C
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
1-3. Dry operation
- (04-4) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS