4-8. Reactor assy
¢
Outdoor unit
Models: AOYG36KQTA, AOYG45KQTA, and AOYG54KQTA
Check point 1. Appearance check
No fissures, breaks, damage, etc. at the body and winding section, terminals section?
Check point 2. Electric check
1
Set the tester to the "Resistance" mode, and check for open/short between both ends of the re-
actor wire (or connector).
2
Judge the result of 1 as follows:
Short
Normal
Open
Abnormal (open)
*Reference value of DC resistance of reactor 0.132Ω Max (at 25°C)
4-8. Reactor assy
- (03-61) -
4. Service parts information
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AUXG36KRLB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Страница 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Страница 50: ......
Страница 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Страница 120: ......
Страница 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...