7-13. Outdoor unit low noise operation
The compressor frequency and outdoor unit fan speed are limited to reduce the operation noise by
external input.
Low noise mode
Low noise mode
Outdoor fan speed
Compressor
frequency
rpm
rps
AOYG36KQTA
Level 1
Cooling/Dry
830
44
Heating
Level 2
Cooling/Dry
830
36
Heating
AOYG45KQTA
Level 1
Cooling/Dry
970
70
Heating
Level 2
Cooling/Dry
970
50
Heating
AOYG54KQTA
Level 1
Cooling/Dry
970
70
Heating
1,040
Level 2
Cooling/Dry
970
50
Heating
1,040
NOTES:
• During the defrost operation, the compressor operates by the speed for defrost operation.
• Even during the low noise operation, the operations of current overload, economy, and peak cut
are effective and the outdoor unit operates by lowest current of them.
Capacity priority mode
• Operation condition
The function setting is set to 1.
• Capacity check condition
– Shortage: Compressor frequency > limited compressor frequency for low noise mode
– Enough: Compressor frequency ≤ limited compressor frequency for low noise mode
• Operation
When detecting the shortage capacity or enough capacity condition continuous 30 minutes, the
mode is changed as follows:
– Automatic switching 1 (Level 1 setting)
Enough for 30 min
Shortage for 30 min
Normal operation
Low noise mode 1
– Automatic switching 2 (Level 2 setting)
Low noise
mode 2
Normal
operation
Low noise
mode 1
Enough for 30 min
Shortage for 30 min
Enough for 30 min
Shortage for 30 min
7-13. Outdoor unit low noise operation
- (04-32) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG36KRLB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Страница 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Страница 50: ......
Страница 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Страница 120: ......
Страница 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...