2-17. E: 62. Outdoor unit main PCB error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 62
Detective actuator
Outdoor unit
Main PCB
Access to EEPROM failed due to some cause after
outdoor unit started.
Forecast of cause
External cause (Noise, temporary open, voltage drop)
Main PCB failure
Check point 1. Reset power supply and operate
Does error indication show again?
↓
Check point 2. Replace main PCB
Change main PCB.
↓
End
Check point 1-2. Check external cause
•
Check if temporary voltage drop was not
generated.
•
Check if momentary open was not generat-
ed.
•
Check if ground is connection correctly or
there are no related cables near the power
line.
↓
End
2-17. E: 62. Outdoor unit main PCB error (Outdoor unit)
- (03-22) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AUXG36KRLB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Страница 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Страница 50: ......
Страница 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Страница 120: ......
Страница 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...