2-1 INPUT / OUTPUT LIST
2. OUTDOOR UNIT
02-01
Input / output or kind of detail
Control range
Discharge pressure sensor <HIGH> Pressure sensor
Measure range 0.0 to 5.0MPa
Suction pressure sensor <LOW> Pressure sensor
Measure range 0.0 to 1.7MPa
Discharge temperature sensor <TH1> Themistor <Blue> Measure range 10 to 130
Heat exchanger temperature sensor <TH5> Themistor <Pink> Measure range -35 to 70
Sub-cool heat exchanger (inlet) sensor <TH8> Themistor <White> Measure range -35 to 70
Sub-cool heat exchanger (outlet) sensor<TH9> Themistor <Brown> Measure range -35 to 70
Liquid temperature sensor <TH7> Themistor <Green> Measure range -35 to 70
Suction temperature sensor <TH4> Themistor <Red>
Measure range -35 to 70
Outdoor temperature sensor <TH3> Themistor < - > Measure range -25 to 58
Operation current sensor
Current transformer
Rotary SW & DIP-SW & Push SW
Electronic expansion valve 1 (Main)
EEV coil
Operating voltage DC12V
Electronic expansion valve 2 (SC-Hex)
EEV coil
Operating voltage DC12V
4-way valve
4-way valve coil
AC220-240V, 50/60Hz 6/5 W
Solenoid valve
Comp pressure equalizing valve
AC220-240V, 50Hz, 6W
Crank case heater
For Inverter Compressor
AC240V, 25W
Base heater
Field supply
AC220-240V, 35W
LON WORKS
Inverter communication
External input 1 (CN131)
(Low noise mode operation)
External input 2 (CN132)
(Cooling / Heating priority)
External input 3 (CN133)
(Outdoor unit operation peak control)
External input 4 (CN134)
(Emergency stop operation)
Dry contact input
Single LED 101
Single LED 102
LED display
Address and function setting
Display the information on operation, error and setting with single LED and
7 segment LED.
Control output: DC 0/12-24V, Max.30mA
Control output: DC 0/12-24V, Max.30mA
External output 1 (CN136) (Error display)
External output 2 (CN137) (Operation display)
ON (Error) / OFF (Normal)
ON (Operation) / OFF (Stop)
Communication
Input / Output
External
Input / Output
I
N
P
U
T
O
U
T
P
U
T
Compressor temperature sensor <TH10> Themistor < - > Measure range 10 to 130
Pressure switch
Pressure switch
Open 4.2MPa Short 3.2MPa
Fan motor 1 (Upper)
DC Brushless motor
7 Segment LED
Compressor
Magnetic relay
Operation coil AC220-240V, 50Hz
Indoor unit Outdoor unit
Fan motor 2 (Lower)
DC Brushless motor
Содержание Airstage J-II
Страница 1: ...Small VRF system for light commercial and home use SERVICE MANUAL ...
Страница 2: ......
Страница 6: ......
Страница 7: ...1 TEST RUN ...
Страница 8: ......
Страница 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 28: ......
Страница 42: ......
Страница 43: ...3 INDOOR UNIT OPERATION ...
Страница 44: ......
Страница 63: ...4 TROUBLE SHOOTING ...
Страница 73: ......
Страница 170: ......
Страница 171: ...5 APPENDING DATA UNIT ...
Страница 172: ......
Страница 174: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Страница 175: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 03 ...
Страница 176: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 04 ...
Страница 177: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 05 ...
Страница 178: ...MODEL ARXB45 05 06 ...
Страница 179: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 07 ...
Страница 180: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 08 ...
Страница 181: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 09 ...
Страница 182: ...MODELS AB A12 AB A14 AB A18 AB A24 05 10 ...
Страница 183: ...MODELS AB A12LBTH AB A14LBTH 05 11 AB A18LBTH AB A24LBTH ...
Страница 184: ...05 12 MODELS AB A30 AB A36 AB A45 AB A54 ...
Страница 185: ...05 13 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Страница 186: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Страница 187: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Страница 188: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Страница 189: ...05 17 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Страница 190: ...05 18 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit ...
Страница 195: ...6 DISASSEMBLY PROCESS ...
Страница 196: ......