DIP switch setting
•
SW100: Remote controller address setting
When operating a number of indoor units by using a wired remote controller, DIP switch set-
ting for assigning unit number to each indoor unit is required.
The slide switches are normally set to make the unit number 00.
Remote
controller
address
Switch number
Factory setting
1
2
3
4
00
OFF
OFF
OFF
OFF
♦
01
ON
OFF
OFF
OFF
02
OFF
ON
OFF
OFF
03
ON
ON
OFF
OFF
04
OFF
OFF
ON
OFF
05
ON
OFF
ON
OFF
06
OFF
ON
ON
OFF
07
ON
ON
ON
OFF
08
OFF
OFF
OFF
ON
09
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON
00
01
02
Remote controller address
Indoor unit
Remote controller
•
SW101-Switch 1: Drainage function setting
Switch 1
Drainage function
Factory setting
ON
Disabled
OFF
Enabled
♦
•
SW101-Switch 2: Auto louver grille setting
When Auto louver grille kit (optional parts) is attached, set to “Enabled”.
Switch 2
Auto louver grille setting
Factory setting
ON
Enabled
OFF
Disabled
♦
•
SW101-Switch 3: Fan delay setting
When the indoor unit is stopped while operating in conjunction with auxiliary heater, the indoor
unit fan operation will continue for 1 minute.
Switch 3
Fan delay
Factory setting
ON
Enabled
OFF
Disabled
♦
- 232 -
14-1. Compact cassette, Mini duct, Slim duct types indoor unit (setting by DIP switch)
14. Function settings
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE