2-2. Mini duct type
Model name
ARXG07KSLAP
ARXG09KSLAP
ARXG12KSLAP
ARXG14KSLAP
Power supply
1Ø 230 V ~50 Hz
Available voltage range
198—264 V
Capacity
kW class
2.0
2.5
3.5
4.0
Input power
Fan
HIGH
W
33
40
47
72
MED
23
23
26
44
LOW
20
20
22
30
QUIET
18
18
18
18
Running current
A
0.29
0.33
0.38
0.58
Fan
Airflow rate
Cooling
HIGH
m
3
/h
550
600
650
800
MED
440
450
490
640
LOW
390
400
430
530
QUIET
360
360
360
360
Heating
HIGH
550
600
650
800
MED
440
450
490
640
LOW
390
400
430
530
QUIET
360
360
360
360
Type × Q'ty
Sirocco fan × 2
Motor output
W
75
Recommended static pressure
Pa
0 to 30
0 to 50
Sound pressure level *
Cooling
HIGH
dB (A)
29
29
31
35
MED
26
26
27
30
LOW
24
24
25
27
QUIET
23
23
23
23
Heating
HIGH
29
29
31
35
MED
26
26
27
30
LOW
24
24
25
27
QUIET
23
23
23
23
Sound power level
Cooling
dB (A)
52
54
55
60
Heating
53
56
57
62
Heat exchanger type
Dimensions (H × W × D)
mm
336 × 490 × 26.6
Fin pitch
mm
1.3
Rows × Stages
2 × 16
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Steel sheet
Color
—
Dimensions
(H × W × D)
Net
mm
198 × 700 × 450
Gross
250 × 930 × 580
Weight
Net
kg
15.5
Gross
19.0
Connection pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Gas
Ø9.52 (Ø3/8)
Method
Flare
Drain hose
Material
Hard PVC
Tip diameter
mm
Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
NOTES:
• Values mentioned in the table are based on the following conditions:
– Static pressure: 10 Pa
• The protective function might work when using it outside the operation range.
• *: Sound pressure level:
– These are the measured values in the manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 12 -
2-2. Mini duct type
2. Specifications
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT