Model name
ARXG18KLLAP
Power supply
1Ø 230 V ~50 Hz
Available voltage range
198—264 V
Capacity
kW class
5.0
Input power
W
73
Running current
A
0.44
Fan
Airflow rate
Cooling
HIGH
m
3
/h
940
MED
880
LOW
820
QUIET
750
Heating
HIGH
940
MED
880
LOW
820
QUIET
750
Type × Q'ty
Sirocco fan × 3
Motor output
W
81
Recommended static pressure
Pa
0 to 90
Sound pressure level *
Cooling
HIGH
dB (A)
32
MED
30
LOW
29
QUIET
27
Heating
HIGH
32
MED
30
LOW
29
QUIET
27
Sound power level
Cooling
dB (A)
58
Heating
58
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 700 × 39.9
Fin pitch
mm
1.3
Rows × Stages
3 × 14
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Steel sheet
Color
—
Dimensions
(H × W × D)
Net
mm
198 × 900 × 620
Gross
276 × 1,168 × 772
Weight
Net
kg
20
Gross
26
Connection
pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Gas
Ø12.70 (Ø1/2)
Method
Flare
Drain hose
Material
PVC
Tip diameter
mm
Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
NOTES:
• Values mentioned in the table are based on the following conditions:
– Static pressure: 25 Pa
• The protective function might work when using it outside the operation range.
• *: Sound pressure level:
– These are the measured values in the manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 15 -
2-3. Slim duct type
2. Specifications
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE