Indoor unit
type
Model name
PCB* fuse
Fan motor thermal protector
Terminal
thermal
fuse
Float
switch
Wall mounted
ASYG07KGTB
250 V, 3.15 A
Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
102 °C Off
―
ASYG09KGTB
ASYG12KGTB
Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG14KGTB
ASYG18KMTB
Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG22KMTB
ASYG24KMTB
ASYG07KMTB
Activate: More than 95 °C
Fan motor speed down
Reset: 95 °C or less
Fan motor speed recover
ASYG09KMTB
ASYG12KMTB
ASYG14KMTB
Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG07KMCC
Activate: 170
+25
-30
°C
Fan motor stop
Reset: 145
+25
-30
°C
Fan motor restart
―
ASYG09KMCC
ASYG12KMCC
ASYG14KMCC
ASYG07KETA
ASYG07KETA-B
Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
102 °C Off
ASYG09KETA
ASYG09KETA-B
ASYG12KETA
ASYG12KETA-B
ASYG14KETA
ASYG14KETA-B
Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
Ceiling
ABYG18KRTA
250 V, 3.15 A
Activate: 135 ±15 °C
Fan motor stop
Reset: 105 ±15 °C
Fan motor restart
108 °C Off
―
ABYG22KRTA
250V, 5.0 A
Floor
AGYG09KVCA
250V, 5.0 A
Activate: 150 ±15 °C
Fan motor stop
Reset: 120 ±15 °C
Fan motor restart
110 °C Off
―
AGYG12KVCA
AGYG14KVCA
*: Printed Circuit Board
- 149 -
10. Safety devices
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE