SERVICE PARTS INFORMATION 4
Check Point 2 : Check Coil of EEV
Yellow - Brown
Orange - Red
Blue - Brown
White - Red
Read wire
46
4
Resistance value
Check Point 1 : Check Connections
Check Point 3 : Check Voltage from Main PCB.
Check Point 4 : Check Noise at start up
DC
at 20°C
Outdoor unit Electronic Expansion Valve
( EEV )
Check connection of connector
( Loose connector or open cable )
Remove connector, check each winding
resistance of Coil.
If Resistance value is abnormal, replace EEV.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
02-52
EXPANSION
VALVE COIL A
EXPANSION
VALVE COIL B
CN27
WHITE
YELLOW
ORANGE
BLUE
BROWN
RED
1
2
3
4
5
6
E V
CN27
WHITE
YELLOW
ORANGE
BLUE
BROWN
RED
1
2
3
4
5
6
E V
EXPANSION
VALVE COIL A
EXPANSION
VALVE COIL B
EXPANSION
VALVE COIL C
EXPANSION
VALVE COIL D
CN27
CN50
CN51
RED
WHITE
YELLOW
ORANGE
BLUE
BROWN
RED
BLACK
WHITE
WHITE
WHITE
WHITE
WHITE
BROWN
BLUE
ORANGE
YELLOW
WHITE
WHITE
GREEN
BLACK
GREEN
GREEN
GREEN
GREEN
RED
BROWN
BLUE
ORANGE
YELLOW
WHITE
GREEN
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
2
1
1
3
4
5
6
7
4
5
6
7
E V
E V
E V
CN52
GREEN
BLACK
GREEN
GREEN
GREEN
GREEN
RED
BROWN
BLUE
ORANGE
YELLOW
WHITE
GREEN
1
2
3
4
5
6
1
2
3
4
5
6
1
3
4
5
6
7
E V
For AO*18LMAK2 / AO*24LMAM2
For AO*30LMAW4
Содержание AB*14LBAJ
Страница 38: ...2 TROUBLE SHOOTING R410A INVERTER MULTI Universal Floor Ceiling Duct Cassette Wall Mounted Floor type ...
Страница 95: ...3 REPLACEMENT PARTS R410A INVERTER MULTI Universal Floor Ceiling Duct Cassette Wall Mounted Floor type ...
Страница 97: ...Thermistor Heat exchanger temp 2 way valve Liquid 3 way valve Gas 03 02 Thermo Holder Thermistor Outdoor Temp ...
Страница 116: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2008 Printed in Japan ...