![Fujitsu AB*14LBAJ Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/fujitsu/ab-14lbaj/ab-14lbaj_service-instruction_118000058.webp)
Trouble shooting 10
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
Indoor Fan Motor abnormal
Indoor Unit Controller PCB Circuit
Indoor Fan Motor
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Control PCB failure
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
When the condition that actual frequency of Indoor Fan is below 1/3
of target frequency is continued more than 56 seconds.
Or the condition of fan speed is 0rpm is continued more than 56 seconds.
02-20
Indicate or Display:
Check Point 3 : Replace Controller PCB
If Check Point 1,2 do not improve the symptom, change Controller PCB.
Refer to error code table.
Содержание AB*14LBAJ
Страница 38: ...2 TROUBLE SHOOTING R410A INVERTER MULTI Universal Floor Ceiling Duct Cassette Wall Mounted Floor type ...
Страница 95: ...3 REPLACEMENT PARTS R410A INVERTER MULTI Universal Floor Ceiling Duct Cassette Wall Mounted Floor type ...
Страница 97: ...Thermistor Heat exchanger temp 2 way valve Liquid 3 way valve Gas 03 02 Thermo Holder Thermistor Outdoor Temp ...
Страница 116: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2008 Printed in Japan ...