![Fujitsu AB*14LBAJ Скачать руководство пользователя страница 71](http://html.mh-extra.com/html/fujitsu/ab-14lbaj/ab-14lbaj_service-instruction_118000071.webp)
Trouble shooting 23
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
Connected Indoor unit error
Outdoor Unit Main PCB Circuit
When the total capacity of the connected indoor units exceed
the connectable range of the total capacity.
1. The selection of connected indoor unit is incorrect 2.Main PCB failure
Check Point 1 : Check the total capacity of indoor unit
Check the total capacity of the connected indoor units.
02-33
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, change Main PCB.
Trouble shooting 24
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Main CPU - Sub CPU
communication error
Outdoor Unit Main PCB Circuit
When it cannot receive an effective signal for 10sec between
the Main CPU and Sub CPU in outdoor unit.
1. Main PCB failure
Check Point 1 : Replace Main PCB
Change Main PCB.
Refer to error code table.
Refer to error code table.
Содержание AB*14LBAJ
Страница 38: ...2 TROUBLE SHOOTING R410A INVERTER MULTI Universal Floor Ceiling Duct Cassette Wall Mounted Floor type ...
Страница 95: ...3 REPLACEMENT PARTS R410A INVERTER MULTI Universal Floor Ceiling Duct Cassette Wall Mounted Floor type ...
Страница 97: ...Thermistor Heat exchanger temp 2 way valve Liquid 3 way valve Gas 03 02 Thermo Holder Thermistor Outdoor Temp ...
Страница 116: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2008 Printed in Japan ...