Trouble shooting 8
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
17.8
26.3
20°C
40.0
62.5
79.1
101
130
169
Resistance Value (k )
15°C
10°C
5°C
0°C
Temperature
OK
OK
OK
OK
12.3
30°C
50°C
40°C
60°C
0.52
180°C
0.79
160°C
1.22
2.00
3.43
4.60
6.27
8.69
Resistance Value (k )
140°C
120°C
100°C
90°C
80°C
70°C
Temperature
Outdoor Discharge Pipe Temperature
Thermistor Error
Outdoor Unit Main PCB Circuit
Discharge Pipe Temperature Thermistor
When Discharge Pipe Temperature Thermistor open or short-circuit
is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-18
TH
E
R
M
IS
TO
R
(D
IS
C
H
A
R
G
E
)
TH
E
R
M
IS
TO
R
(P
IP
E
)
TH
E
R
M
IS
TO
R
(O
U
TD
O
O
R
)
TH
E
R
M
IS
TO
R
(H
E
A
T
S
IN
K
)
B
R
O
W
N
B
LA
C
K
B
LA
C
K
B
LU
E
CN25 CN23 CN22 CN21
1 2
1 2
1 2
1 2
Refer to error code table.
Содержание AB*14LBAJ
Страница 38: ...2 TROUBLE SHOOTING R410A INVERTER MULTI Universal Floor Ceiling Duct Cassette Wall Mounted Floor type ...
Страница 95: ...3 REPLACEMENT PARTS R410A INVERTER MULTI Universal Floor Ceiling Duct Cassette Wall Mounted Floor type ...
Страница 97: ...Thermistor Heat exchanger temp 2 way valve Liquid 3 way valve Gas 03 02 Thermo Holder Thermistor Outdoor Temp ...
Страница 116: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2008 Printed in Japan ...