Hardware Installation
Installing/Removing the Rack Model
Figure 12: Mounting the telescopic rail into the Classic Rack
Ê
Using the supplied Allen key (No. 5) secure the two telescopic rails with two
screws M5 each in the rack at the right and left support uprights.
Please note that the guide nubs of the telescopic rails next to the spring nuts
must fit into the holes in the support uprights.
Ê
Mount the server (see section “Installing the Server” on page 44).
Mounting the Articulated Cable Carrier (Cable Management)
V
CAUTION!
In contrast to the instruction in the Technical Manual for the 19-inch
(Classic) Rack the articulated cable carrier is fastened only to the
support upright - not at the server.
Ê
To secure the articulated cable carrier place two spring nuts in the groove of
the rear right support upright. The mounting height must agree with the
height of the connecting cables at the server.