![Fuji Electric ZKJ Series Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/fuji-electric/zkj-series/zkj-series_instruction-manual_2341903080.webp)
6 - 40
+RZWRVHWFKDQJHWKHUDQJH!
The measuring range can be arbitrarily selected in
WKHPLQLPXPDQGWKHPD[LPXPUDQJHVSHFL¿HGDW
the time of purchase. The range to be used can be
selected 1 or 2.
0RYHWKHFXUVRUWRWKHLWHPWREHVHWE\SUHVV
-
ing the
or the
key, and then press the
ENT
key.
0RYHWKHFXUVRUWRWKH&KFRPSRQHQWZKRVH
setting is to be changed by pressing the
or
the
key, and then press the
ENT
key.
0RYHWKHFXUVRUWRWKHLWHPZKRVHVHWWLQJLVWR
be changed by pressing the
or the
key,
and then press the
ENT
key.
(4) Press the
or the
key to change the value.
Press the
key to select the next digit. In a
state where the decimal point is highlighted,
press the
or the
key, and the decimal
point position can be changed.
(5) When necessary change is made, press the
ENT
key.
The value for range 1 and range 2 must fall within
the range from the MIN and the MAX range
(including the MIN and the MAX range), and
at the same time range 1 must be smaller than
range 2.
The number of ranges is 1 or 2.
Settable range
Be sure to perform zero / span calibration when
the range setting is changed.
Otherwise, the measurement value may not be
output properly.
CAUTION
ENT
Range setting, change end
ENT
ENT
ENT