2-11
2.3.3 Terminal arrangement diagram and screw specifications
The table below shows the main circuit screw sizes, tightening torque and terminal arrangements. Note that the
terminal arrangements differ according to the inverter types. Two terminals designed for grounding shown as the
symbol, in Figures A to J make no distinction between a power supply source (a primary circuit) and a motor
(a secondary circuit).
(1) Arrangement of the main circuit terminals
Table 2.6 Main Circuit Terminal Properties
Power supply
voltage
Nominal applied
motor(HP)
Inverter type
Terminal
screw size
Tightening
torque(N·m)
Grounding
screw size
Tightening
torque(N·m)
Refer to:
1 FRN001F1S-2U
2 FRN002F1S-2U
3 FRN003F1S-2U
5 FRN005F1S-2U
M4 1.8 M4 1.8
Figure
A
7 FRN007F1S-2U
10 FRN010F1S-2U
M5 3.8 M5 3.8
15 FRN015F1S-2U
Figure B
20 FRN020F1S-2U
25 FRN025F1S-2U
M6 5.8 M6 5.8
Figure C
30 FRN030F1S-2U
Figure D
40 FRN040F1S-2U
M8 13.5
Figure E
50 FRN050F1S-2U
60 FRN060F1S-2U
75 FRN075F1S-2U
100 FRN100F1S-2U
M10 27
M8 13.5
Figure G
Three-
phase
208 V
125 FRN125F1S-2U
M12 48 M10 27
Figure
J
1 FRN001F1S-4U
2 FRN002F1S-4U
3 FRN003F1S-4U
5 FRN005F1S-4U
7 FRN007F1S-4U
M4 1.8 M4 1.8
Figure
A
10 FRN010F1S-4U
15 FRN015F1S-4U
M5 3.8 M5 3.8
20 FRN020F1S-4U
Figure B
25 FRN025F1S-4U
30 FRN030F1S-4U
M6 5.8 M6 5.8
Figure C
40 FRN040F1S-4U
Figure D
50 FRN050F1S-4U
60 FRN060F1S-4U
Figure E
75 FRN075F1S-4U
100 FRN100F1S-4U
M8 13.5
Figure F
125 FRN125F1S-4U
150 FRN150F1S-4U
M8 13.5
Figure G
200 FRN200F1S-4U
M10 27
Figure H
250 FRN250F1S-4U
300 FRN300F1S-4U
350 FRN350F1S-4U
Figure I
400 FRN400F1S-4U
450 FRN450F1S-4U
Figure K
500 FRN500F1S-4U
600 FRN600F1S-4U
Figure L
700 FRN700F1S-4U
800 FRN800F1S-4U
Three-
phase
460 V
900 FRN900F1S-4U
M12 48
M10 27
Figure M
Terminal R0, T0 (Common to all types): Screw size M3.5, Tightening torque 10.6lb-in(1.2 (N·m))
Terminal R1, T1: Screw size M3.5, Tightening torque 8lb-in(0.9 (N·m)) (for the models of 208 V series 50HP or above, for
460 V series 60HP or above
Содержание FRENIC-ECO
Страница 111: ...5 3 F codes Fundamental Functions The shaded function codes are applicable to the quick setup...
Страница 114: ...5 6 F code continued...
Страница 115: ...5 7 E codes Extension Terminal Functions...
Страница 116: ...5 8 E code continued...
Страница 119: ...5 11 E code continued...
Страница 121: ...5 13 P codes Motor Parameters The shaded function codes are applicable to the quick setup...
Страница 122: ...5 14 H codes High Performance Functions...
Страница 123: ...5 15 H code continued...
Страница 126: ...5 18 J code continued...
Страница 127: ...5 19 J code continued...
Страница 128: ...5 20 y codes Link Functions...
Страница 129: ...5 21 y code continued...
Страница 141: ...5 33 Example of Operating Characteristics...
Страница 217: ...8 6 8 3 Common Specifications...
Страница 218: ...8 7...
Страница 223: ...8 12 8 5 External Dimensions 8 5 1 Standard models Unit inch mm 10 2 260...
Страница 227: ...8 16 8 5 3 Multi function Keypad Unit inch mm...
Страница 246: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 11 K07 K07 10CM...