5-65
H06
Cooling Fan ON/OFF Control
To prolong the life of the cooling fan and to reduce fan noise during running, the cooling fan is
stopped when the temperature inside the inverter drops below a certain level while the inverter is
stopped. However, since frequent switching of the cooling fan shortens its life, it is kept running
for 10 minutes once it is started.
This function code (H06: Cooling fan ON/OFF control) allows you to specify whether the cooling
fan is to be kept running all the time or to be controlled ON/OFF.
Data for H06
Cooling fan ON/OFF
0
Disable (Always in operation)
1
Enable (ON/OFF controllable)
H07
Acceleration/Deceleration Pattern
H07 specifies the acceleration and deceleration patterns (Patterns to control output frequency).
Linear acceleration/deceleration
The inverter runs the motor with the constant acceleration and deceleration.
S-curve acceleration/deceleration
To reduce the impact on the inverter-driven motor and/or its mechanical load during
acceleration/deceleration, the inverter gradually accelerates/decelerates the motor in both the
acceleration/deceleration starting and ending zones. Two types of S-curve
acceleration/deceleration are available; 5% (weak) and 10% (strong) of the maximum frequency,
which are shared by the four inflection points. The acceleration/deceleration time command
determines the duration of acceleration/deceleration in the linear period; hence, the actual
acceleration/deceleration time is longer than the reference acceleration/deceleration time.
Acceleration/deceleration time
<S-curve acceleration/deceleration (weak): when the frequency change is more than 10% of the
maximum frequency>
Acceleration/deceleration time (s):
(2
×
5/100 + 90/100+ 2
×
5/100)
×
(reference acceleration
or deceleration time)
= 1.1
×
(reference acceleration or deceleration time)
<S-curve acceleration/deceleration (strong): when the frequency change is more than 20% of the
maximum frequency>
Acceleration/deceleration time (s):
(2
×
10/100 + 80/100 + 2
×
10/100)
×
(reference
acceleration/deceleration time)
= 1.2
×
(reference acceleration/deceleration time)
Содержание FRENIC-ECO
Страница 111: ...5 3 F codes Fundamental Functions The shaded function codes are applicable to the quick setup...
Страница 114: ...5 6 F code continued...
Страница 115: ...5 7 E codes Extension Terminal Functions...
Страница 116: ...5 8 E code continued...
Страница 119: ...5 11 E code continued...
Страница 121: ...5 13 P codes Motor Parameters The shaded function codes are applicable to the quick setup...
Страница 122: ...5 14 H codes High Performance Functions...
Страница 123: ...5 15 H code continued...
Страница 126: ...5 18 J code continued...
Страница 127: ...5 19 J code continued...
Страница 128: ...5 20 y codes Link Functions...
Страница 129: ...5 21 y code continued...
Страница 141: ...5 33 Example of Operating Characteristics...
Страница 217: ...8 6 8 3 Common Specifications...
Страница 218: ...8 7...
Страница 223: ...8 12 8 5 External Dimensions 8 5 1 Standard models Unit inch mm 10 2 260...
Страница 227: ...8 16 8 5 3 Multi function Keypad Unit inch mm...
Страница 246: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 11 K07 K07 10CM...