5-25
The table below shows relationship between keying and run commands in running per a keypad
(F02 = 0, rotation direction is defined by the digital inputs).
Keying on the keypad
Digital inputs
key
key
key
(FWD)
(REV)
Results
(Final command)
-
-
ON
-
-
Stop
ON OFF OFF OFF OFF
Stop
ON OFF OFF ON OFF
Run forward
ON OFF OFF OFF ON Stop
ON OFF OFF ON
ON Stop
-
-
ON
-
-
Stop
OFF
ON OFF OFF OFF Stop
OFF
ON OFF ON OFF
Stop
OFF
ON OFF OFF ON
Run reverse
OFF
ON OFF ON
ON Stop
The table below shows relationship between keying and setting F02.
Keying on the keypad
F02 setting
key
key
2
Run forward
Stop
3 Stop
Run reverse
• Digital input commands (FWD) and (REV) are valid for specifying the motor rotation
direction, and the commands (FWD2) and (REV2) are invalid.
• If you have assigned the (FWD) or (REV) function to the [FWD] or [REV] terminal,
you cannot change the setting of function code F02 while the terminals [FWD] and/or
[REV] are on.
• Make sure that terminals [FWD] and [REV] are off before changing the (FWD) or
(REV) function from the function other than the (FWD) and (REV) functions to (FWD)
or (REV) function. Because, if under this condition you assign the (FWD) or (REV)
function to the [FWD] or [REV] terminal while the terminals [FWD] and/or [REV] are
on, the motor would start running.
When "Local" is selected in Remote/Local switching, the operation of the keypad concerning run
commands varies with the setting of F02. For details, refer to "
■
Switching the operation mode
between remote and local" in Chapter 3, Section 3.3.1.
F03
Maximum Frequency
F03 specifies the maximum frequency at which the motor can run. Specifying the frequency out of
the range rated for the equipment driven by the inverter may cause damage or a dangerous
situation. Set a maximum frequency appropriate for the equipment.
The inverter can easily accept high-speed operation. When changing the speed setting, carefully
check the specifications of motors or equipment beforehand.
Otherwise injuries could occur.
Modifying F03 data to apply a higher output frequency requires also changing F15 data
specifying a frequency limiter (high).
Содержание FRENIC-ECO
Страница 111: ...5 3 F codes Fundamental Functions The shaded function codes are applicable to the quick setup...
Страница 114: ...5 6 F code continued...
Страница 115: ...5 7 E codes Extension Terminal Functions...
Страница 116: ...5 8 E code continued...
Страница 119: ...5 11 E code continued...
Страница 121: ...5 13 P codes Motor Parameters The shaded function codes are applicable to the quick setup...
Страница 122: ...5 14 H codes High Performance Functions...
Страница 123: ...5 15 H code continued...
Страница 126: ...5 18 J code continued...
Страница 127: ...5 19 J code continued...
Страница 128: ...5 20 y codes Link Functions...
Страница 129: ...5 21 y code continued...
Страница 141: ...5 33 Example of Operating Characteristics...
Страница 217: ...8 6 8 3 Common Specifications...
Страница 218: ...8 7...
Страница 223: ...8 12 8 5 External Dimensions 8 5 1 Standard models Unit inch mm 10 2 260...
Страница 227: ...8 16 8 5 3 Multi function Keypad Unit inch mm...
Страница 246: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 11 K07 K07 10CM...