5.3.4 Blowing in fuel for an empty store with rotary agitator
NOTICE
Filling an empty store space with a rotary agitator:
With the store space completely empty or almost empty, the rotary agitator arms /
spring blades are fully extended. If the rotary agitator arms / spring blades are
covered in this position with a large amount of fuel, the weight of the fuel will stop
them from working properly.
Therefore, when filling an empty store space or when the rotary agitator arms are
extended:
❒ First of all place a small amount of fuel (approx. 2 – 3 m³) on and around the
head of the rotary agitator
❒ Only add the rest of the fuel once the rotary agitator arms are back on the
head of the rotary agitator
❒ It is important you follow the procedure given below!
❒ Switch off the power supply to the entire system
➥ Depending on the model via boiler, expansion switch cabinet, etc.
❒ Pile up residual fuel (in the corners and on the walls) in the fuel store on and
around the head of the rotary agitator by hand and distribute on discharge screw
➥ The head of the rotary agitator should be completely covered
❒ Follow the instructions on working in the fuel store!
NOTICE! Refer to the notice (supplied with the boiler) at the entrance to the store
Operating the system
5
Filling the store with fuel
Installation and Operating Instructions | M1730116_en
39