65
106346-06 - 8/19
FORCE
Installation, Operating & Service Manual
Boiler Model
Burner
Input
(GPH)
Burner
Model
Nozzle
Air
Shutter
(setting)
Air Band
(setting)
Pump
Pressure
(PSI)
Head
Type
(setting)
Insertion
Depth
(Inch)
Approx.
Shipped
CO
2
(%)
Baffle
Location
(pass)
Approx.
Stack
Temp.
Increase
Without
Baffles
°F
(2)
Approx.
Breech
Pressure
(" w.c.)
(3)
Baffles IN
Approx.
Overfire
Pressure
(" w.c.)
(3)
Baffles
OUT
Approx.
Overfire
Pressure
(" w.c.)
(3)
FORCEOL084-E
0.60
AFG
0.50 x
45W
Delavan
6
(1)
0
150
L2
2
11.5
2
2d
---
0
---
+0.005
FORCEOL115-E
0.80
AFG
0.65
x 45B
Delavan
6
0
150
L2
2
11.5
2
nd
& 3
rd
84
0
+0.040
+0.020
FORCEOL140-E
1.00
AFG
0.85
x 60B
Delavan
7
1
150
L1
2
11.5
2
nd
65
0
+0.040
+0.020
FORCEOL182-E
1.30
AFG
1.10 X
60B Hago
7
2
150
V1 (0)
2
11.5
2
nd
---
0
---
+0.030
Notes
(1)
FORCEOL084-E at 0.60 GPH firing rate utilizes a low fire baffle.
(2)
The increased stack temperature with the baffles removed is an approximation, based on a constant supply temperature of 180°F and 11.5% CO
2
. Actual field
conditions may be different.
(3)
These values are minimum and could be as much as -.03" w.c., more without impacting performance. Pressures based on 11.5% CO
2
.
(4)
Single stage fuel pump is standard, two-stage fuel pump is optional. Burner manufacturer has preset single stage fuel pump to settings shown in table above. Two-
stage fuel pump is factory set at 140 PSI and must be readjusted to settings shown above during burner start-up.
Boiler Model
Burner
Input
(GPH)
Head / Air
Adjustment
(setting)
Nozzle
Pump
Pressure
(PSI)
Approx.
Shipped
CO
2
(%)
Baffle
Location
(pass)
Approx.
Stack Temp.
Increase
Without
Baffles °F
(2)
Baffles IN
Minimum
Overfire
Pressure
(" w.c.)
(3)
Baffles OUT
Minimum
Overfire
Pressure
(" w.c.)
(3)
Baffles IN
Minimum
Breech
Pressure
(" w.c.)
(3)
Baffles OUT
Minimum
Breech
Pressure
(" w.c.)
(3)
FORCEOL140-E
1.00
2.75
Delavan
.0.75 x 60°W
180
11.5
2
nd
75
+0.06
+0.045
+0.045
+0.03
FORCEOL182-E
1.30
1.00
Hago
1.00 x 45°B
180
2
nd
70
+0.10
+0.05
+0.08
+0.04
Notes
(2)
The increased stack temperature with the baffles removed is an approximation, based on a constant supply temperature of 180°F and 11.5% CO
2
.
Actual field values may be different.
(3)
These values are representative for max vent and air intake piping conditions @ 180°F supply water temperature and 11.5% CO
2
.
Actual field values may be different.
(4)
Single stage fuel pump is standard, two-stage fuel pump is optional. Burner manufacturer has preset single stage fuel pump to settings shown in table above.
Two-stage fuel pump is factory set at 140 PSI and must be readjusted to settings shown above during burner start-up.
16
Burner Specifications
Содержание FORCEOL115-E
Страница 56: ...56 106346 06 8 19 FORCE Installation Operating Service Manual Bare Boiler Assembly 15 Service Parts continued...
Страница 58: ...58 106346 06 8 19 FORCE Installation Operating Service Manual Jacket Assembly 15 Service Parts continued...
Страница 61: ...61 106346 06 8 19 FORCE Installation Operating Service Manual Beckett AFG Burner 15 Service Parts continued...
Страница 63: ...63 106346 06 8 19 FORCE Installation Operating Service Manual Beckett NX Burner 15 Service Parts continued...