CONNECTING APPLIANCE ADAPTER TO
BOILER FLUE OUTLET COLLAR
(See Figure 21) reimburse
1. Apply a bead of supplied high temperature sealant
to boiler flue outlet collar approximately 1" from
collar end.
2. Remove any oil and grease from inside of supplied
Appliance (Boiler Flue Outlet) Adapter, and, apply
a bead of high temperature sealant to inside of
the adapter, ½" from end.
3. With twisting motion, assemble the appliance
adapter onto boiler flue outlet collar.
4. Using a mallet and a block of wood, carefully
tap the adapter onto the outlet collar. Insure no
damage is done to the adapter and the flue outlet
collar.
5. Assemble supplied adapter clamp halves with
5/16-18 bolts and square nuts; install the adapter
clamp onto the appliance adapter and tighten
securely.
6. If required, install anchoring screws (installer
provided) thru four holes in the clamp into the
flue outlet collar.
7. Apply sealant around the adapter end mated to
the flue outlet collar.
8. Install supplied 3/8” sampling port plug screw
hand tight into the adapter sampling port.
9.
After initial boiler start-up and burner
testing/adjustment are completed
,
apply high
temperature sealant under the head of sampling
port plug screw, and, install the screw in the
sampling port tightening securely.
F . CONNECTING FLEX OIL VENT PIPE TO
APPLIANCE ADAPTER AND DIRECT VENT
TERMINATION
1. Flexible double wall oil vent pipe is available
pre-cut in 5 ft and 20 ft length. If necessary, the
vent pipe may be cut to required length with a
hacksaw or cutoff saw.
CAUTION
Use safety glasses and other appropriated
safety gear when cutting the vent pipe.
2. The double wall flexible vent pipe consists of the
smaller inner corrugated stainless steel pipe and
larger corrugated aluminum pipe, separated by
fiberglass insulation layer.
Boiler Model
Boiler Flue Outlet
Collar OD (Inch)
Vent Hood
Inner Pipe
Diameter (Inch)
Flex Oil Vent Pipe
Inner Pipe Diameter
(Inch)
* Flue Outlet Collar to
Vent Pipe Adapter (Inch)
FORCEOL140-E
6
5
6 to 5
FORCEOL182-E
NOTE:
* The model specific Direct Vent (FDVS) Kit Cartons contain adapters (reducers) (see Table 6) to connect boiler flue outlet
collar to vent pipe.
Table 6: Flex Vent / Vent Termination Pipe Diameters
Figure 21: Appliance Adapter Installation
7
Direct Venting / Air Intake Piping
(continued)
!
Содержание FORCEOL115-E
Страница 56: ...56 106346 06 8 19 FORCE Installation Operating Service Manual Bare Boiler Assembly 15 Service Parts continued...
Страница 58: ...58 106346 06 8 19 FORCE Installation Operating Service Manual Jacket Assembly 15 Service Parts continued...
Страница 61: ...61 106346 06 8 19 FORCE Installation Operating Service Manual Beckett AFG Burner 15 Service Parts continued...
Страница 63: ...63 106346 06 8 19 FORCE Installation Operating Service Manual Beckett NX Burner 15 Service Parts continued...