30
106346-06 - 8/19
FORCE
Installation, Operating & Service Manual
CAUTION
The inner and outer pipe ends may have sharp
burrs. Use gloves, while handling, compressing
or expanding the vent pipe.
3. Pull outer vent pipe back 1” to 2” from end of
inner vent pipe and remove insulation; firstly,
at vent pipe end to be connected to the vent
termination; secondly, at vent pipe end to
be connected to the appliance adapter. See
Figure 22.
4. Install supplied Cover Sleeve Assembly onto
each end of outer vent pipe, and, move the
assembly a few inches back from the end;
firstly, at vent pipe side to be connected to the
vent termination; secondly, at vent pipe side
to be connected to the appliance (boiler outlet
collar) adapter. See Figure 22.
5. Slide supplied Cover Rings; firstly, over stop
bead on vent termination inner pipe; secondly,
over stop bead on appliance adapter. See
Figure 22.
6. Remove any oil and grease from the end of
vent termination inner pipe, and, from the end
of the appliance adapter.
Figure 22: Vent Pipe Assembly to Vent Termination
Inner Pipe and Appliance Adapter
7. Apply sealant; firstly, between the stop bead
and retainer bead at the end of the vent
termination inner pipe; secondly, between the
stop bead and retainer bead at the end of the
appliance adapter. See Figure 23.
8. Assemble supplied inner pipe clamp halves
with 1/4-20 bolts and square nuts; position the
inner pipe clamps ¼” from the end of inner
vent pipe, on vent pipe opposite ends.
9. Remove any oil and grease from inside of each
end of the inner vent pipe.
10. Apply a thick bead of sealant to inside of each
end of the inner vent pipe, ½” from pipe end,
working the sealant into the inner vent pipe
corrugations. See Figure 23.
11. Firstly, push one end of the inner vent pipe onto
the vent termination inner pipe, all the way up
to the stop bead. Secondly, push the opposite
end of the inner vent pipe onto the appliance
adapter, all the way up to the stop bead.
12. Tighten the inner pipe clamp bolts at both vent
pipe ends, until clamp halves are within 1/8”
apart. See Figure 24.
13. Starting with vent termination end, slide the
cover sleeve assembly and the cover ring
together to engage the ring in the groove of the
sleeve, then, tighten the built-in cover sleeve
clamp. Repeat above steps at the boiler end.
See Figure 24.
14. If the appliance collar is within less than 18"
of combustible material, wrap minimum 1-1/2"
thick fiberglass insulation (installer provided).
15. To maintain vent pipe 1" clearance to
combustible material, wrap minimum 1-1/2"
thick fiberglass insulation (installer provided)
around the exposed portion of the vent
termination inner pipe and secure with
adhesive-backed aluminum foil tape (installer
provided).
Figure 23: Vent Pipe Ends, Vent Termination and Appliance Adapter Sealing
7
Direct Venting / Air Intake Piping
(continued)
Содержание FORCEOL115-E
Страница 56: ...56 106346 06 8 19 FORCE Installation Operating Service Manual Bare Boiler Assembly 15 Service Parts continued...
Страница 58: ...58 106346 06 8 19 FORCE Installation Operating Service Manual Jacket Assembly 15 Service Parts continued...
Страница 61: ...61 106346 06 8 19 FORCE Installation Operating Service Manual Beckett AFG Burner 15 Service Parts continued...
Страница 63: ...63 106346 06 8 19 FORCE Installation Operating Service Manual Beckett NX Burner 15 Service Parts continued...