4.9 Burner wiring diagram

Picture 16 shows the wirin diagrams of the burners.

pic. 16

4.10 Burner troubleshooting

18

MALFUNCTION

POSSIBLE CAUSE

SOLUTIONS

The burner does not switch on when it 
receives a start signal from the root 
thermostat

Boiler is not powered on

Check voltage at the terminals

Check the fuse

Check the room thermostat

The photo resistance reads a false light

Eliminate the false light

The control unit is connected wrongly

Check the terminal connections

The burner implements pre-washing proce-
dure and then shuts down

The photoresistance is dirty

Clean it

The photoresistance is faulty

Replace it

The flame goes out or does not light

Check the oil pressure

Check that oil flows smootly from the nozzle

Check the air

Check the solenoid valve

Change the nozzle

The burner starts after one failed ignition

The ignition electrodes are wrongly positioned

Position electrodes according to instruc-
tions

The air flow is too high

Regulate the air flow

The nozzle is dirty or damaged

Replace it

The resistor is faulty

Replace it

Ignition 
electrodes

Flame detector

Solenoid valve

Capacitor

Burner-earth

Safety 

thermostat

Limit thermostat

Remote lock-out signal

Oil pre-heater

Содержание CAPRI C

Страница 1: ...CAPRI C IST 03 C 201 01 INSTALLATION USE AND MAINTENANCE GB...

Страница 2: ...Dear Customer Thank you for choosing and buying one of our boilers Please read these instructions carefully in order to install operate and maintain this equipment properly...

Страница 3: ...se of the packaging as all the materials can be recycled The packaging must therefore be sent to specific waste management sites Keep the packaging out of the reach of children as by its nature it may...

Страница 4: ...nnections to fuel oil mains supply page 11 3 2 5 Ventilation page 11 3 2 6 Air intake and flue gas discharge pipes page 11 3 2 7 Types and classification of air intake and flue gas discharge pipes pag...

Страница 5: ...mote control is interrupted or there are signal passage difficulties Once the connection is restored the light will turn off and the boiler will resume operation 7 Indication light red when the light...

Страница 6: ...a fixed value of 50 C in order to speed the response time should there be a demand for domestic hot water The MAINTENANCE function is not enabled when the selector is in the ANTI FREEZE position DOME...

Страница 7: ...osed as pressure increa ses boiler CH safety valve may open and water flow out Should boiler frequently shut down due to insufficient water pres sure have it serviced by an Authorized Service Centre o...

Страница 8: ...th epoxypolye ster powders Unit electronic management card Heating expansion vessel with 8 litre capacity Heating safety valve at 3 bar Three speed heating circulator Single speed domestic hot water c...

Страница 9: ...PRIORITY FLOW METER BR BURNER S2 DHW PROBE PS DHW PUMP TS LIMIT THERMOSTAT TA1 ROOM THERMOSTAT OPTIONAL 1 FLOW G 3 4 M 2 DHW G 1 2 M 3 RETURN G 3 4 M 4 COLD WATER G 1 2 M fig 3 D mm CTF 150 CTFD 120 A...

Страница 10: ...temperature setting range C 50 82 Maximum CH working pressure bar 3 3 CH expansion vessel capacity l 12 12 DHW temperature setting range C 35 57 Maximum DHW working pressure bar 6 6 DHW supply T 30K l...

Страница 11: ...elivery and return pipes Join the unit to the chimney and to the air intake pipe for D versions Connect the burner to the fuel oil supply pipes see sub section 3 2 4 Connect the unit to the power main...

Страница 12: ...ble thermal insu lation min 50 mm IMPORTANT When flue gas system is discharged through pipes diameter 125 mm it is compulsory to install on the air intake pipe an 80 mm diameter terminal similar to th...

Страница 13: ...e connected to the respective G 1 2 fittings on the heating unit The mains pressure must not be more that 6 bar otherwise a pres sure reducer needs to be provided The pressure in the DHW circuit shoul...

Страница 14: ...he safety valve is not blocked Check for water leaks 3 4 2 Switching on and off For instructions on how to switch the heating unit on and off refer to the User Manual 3 4 3 Burner regulation After sta...

Страница 15: ...stem If you need to work with a single pipe unscrew the cap 2 and re move the grub screw 3 Afterwards replace the cap 2 pic 17 Important With twin tube systems before starting up the burner make sure...

Страница 16: ...air can be regulated by turning the socket screw A shown in pic 11 The setting is shown on a graduated scale B The oil pressure can be regulated by turning screw 5 in pic 17 Refer to the technical da...

Страница 17: ...e high voltage wires pic 14 pic 13 4 8 Burner ignition In the event of shutdown the red be pressed to reset The burner ignition cycle is light 7 on the control panel pic 25 summarised in the graphs in...

Страница 18: ...s pre washing proce dure and then shuts down The photoresistance is dirty Clean it The photoresistance is faulty Replace it The flame goes out or does not light Check the oil pressure Check that oil f...

Страница 19: ...ating unit to be serviced and repaired by an authorised Service Centre which can provide properly trained quali fied personnel Before carrying out any maintenance involving the replacement of componen...

Страница 20: ...solved Flow probe is faulty Flow probe is disconnected Replace it Flow probe is faulty Replace it The boiler has shut down and red light no 6 is flashing Boiler will automatically resume operation as...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...Via Cerreto 40 Tel 0365 878 31 e mail fondital fondital it www fondital it The manufacturer reserves the right to modify the data contained herein at any time without notice Uff Pubblicit Fondital IST...

Отзывы: