Version CTFD (type B23; C53; C83)

The heating unit version CTFD (Types B23, C53 and C83) has a 
female fitting at the back with an 80 mm lip seal for connecting to 
a combustion air intake pipe.  
Combustion air must be taken from outside the room in which the 
heating unit is installed by means of a suitable pipe. 
The  maximum  length  of  this  pipe  is  given  in  the  technical  data 
sheet. 
When using bends, remember that a wide radius 90° curve is, in 
term of load losses, equivalent to a straight section of pipe 1 metre 
long, and a narrow radius 90° curve is equivalent to a straight pipe 
1.5 metres long.  
When flue gas is discharged through vertical and horizontal pipes 
diameter 120 mm, and with through wall discharge, when allowed, 
the maximum length of the discharge pipes is shown in the tech-
nical data sheet. 
When using bends, remember that a wide radius 90° curve is, in 
term of load losses, equivalent to a straight section of pipe 1 metre 
long, and a narrow radius 90° curve is equivalent to a straight pipe 
1.5 metres long. 
 

IMPORTANT 
Only enamelled or stainless steel pipes with trade or The ma-
nufacturer gaskets must be used for flue gas discharge.  
With vertical pipes, a special section is required for conden-
sate discharge. 
All  the  installations  both  versions  CTF  and  CTFD  require  a 
special section in the link to the flue allowing measurement of 
the flue gas temperature and CO2 percentage. This is so that 
the burner can be set correctly and the combustion efficiency 
determined. 

IMPORTANT
When running pipes through walls made of flammable mate-
rial, make sure the discharge pipe has suitable thermal insu-
lation (min. 50 mm). 

IMPORTANT
When flue gas system is discharged through pipes diameter 
125 mm, it is compulsory to install on the air intake pipe an 80 
mm diameter terminal similar to those used for the flue gas 
discharge of wall-hung boilers.

 

3.2.7  Types  and  classification  of  air  intake  and  flue  gas  di-
scharge pipes

Type B23

Discharge through the wall (if allowed by the installation standar-
ds) or through the roof or via the boiler flue. The relevant data is 
shown on the technical data sheet, which complies with current 
standards.

Type C83

Connection to the chimney compatible with type C83.

Type C53

The  end  sections  of  the  air  intake  and  flue  gas  discharge  pipes 
must never be in opposing walls. 
Refer to the table in subsection 2.2.

model C23

Max equivalent length of discharge pipe Ø 120 mm: 5 metres

Each added wide radius 90° bend equals 1 metre discharge

Each added narrow radius 90° bend equals 1.5 metre discharge

model C33

Max equivalent length of discharge pipe Ø 120 mm: 4 metres

Each added wide radius 90° bend equals 1 metre discharge

Each added narrow radius 90° bend equals 1.5 metre discharge

model CTFD 23

Max equivalent length 

of air intake pipe Ø 80 mm

Max equivalent length 

of discharge pipe Ø 120 mm

< 1 m

up to 5 m

from 1 to 6 m

up to 6 m

from 6 to 7 m

up to 7 m

Each added wide radius 90° bend equals 1 metre both air intake and discharge

Each added narrow radius 90° bend equals 1.5 metre both air intake and discharge

model CTFD 33

Max equivalent length 

of air intake pipe Ø 80 mm

Max equivalent length 

of discharge pipe Ø 120 mm

from 0 to 4 m

up to 4 m

from 4 to 6 m

up to 6 m

from 6 to 7 m

up to 7 m

Each added wide radius 90° bend equals 1 metre both air intake and discharge

Each added narrow radius 90° bend equals 1.5 metre both air intake and discharge

Содержание CAPRI C

Страница 1: ...CAPRI C IST 03 C 201 01 INSTALLATION USE AND MAINTENANCE GB...

Страница 2: ...Dear Customer Thank you for choosing and buying one of our boilers Please read these instructions carefully in order to install operate and maintain this equipment properly...

Страница 3: ...se of the packaging as all the materials can be recycled The packaging must therefore be sent to specific waste management sites Keep the packaging out of the reach of children as by its nature it may...

Страница 4: ...nnections to fuel oil mains supply page 11 3 2 5 Ventilation page 11 3 2 6 Air intake and flue gas discharge pipes page 11 3 2 7 Types and classification of air intake and flue gas discharge pipes pag...

Страница 5: ...mote control is interrupted or there are signal passage difficulties Once the connection is restored the light will turn off and the boiler will resume operation 7 Indication light red when the light...

Страница 6: ...a fixed value of 50 C in order to speed the response time should there be a demand for domestic hot water The MAINTENANCE function is not enabled when the selector is in the ANTI FREEZE position DOME...

Страница 7: ...osed as pressure increa ses boiler CH safety valve may open and water flow out Should boiler frequently shut down due to insufficient water pres sure have it serviced by an Authorized Service Centre o...

Страница 8: ...th epoxypolye ster powders Unit electronic management card Heating expansion vessel with 8 litre capacity Heating safety valve at 3 bar Three speed heating circulator Single speed domestic hot water c...

Страница 9: ...PRIORITY FLOW METER BR BURNER S2 DHW PROBE PS DHW PUMP TS LIMIT THERMOSTAT TA1 ROOM THERMOSTAT OPTIONAL 1 FLOW G 3 4 M 2 DHW G 1 2 M 3 RETURN G 3 4 M 4 COLD WATER G 1 2 M fig 3 D mm CTF 150 CTFD 120 A...

Страница 10: ...temperature setting range C 50 82 Maximum CH working pressure bar 3 3 CH expansion vessel capacity l 12 12 DHW temperature setting range C 35 57 Maximum DHW working pressure bar 6 6 DHW supply T 30K l...

Страница 11: ...elivery and return pipes Join the unit to the chimney and to the air intake pipe for D versions Connect the burner to the fuel oil supply pipes see sub section 3 2 4 Connect the unit to the power main...

Страница 12: ...ble thermal insu lation min 50 mm IMPORTANT When flue gas system is discharged through pipes diameter 125 mm it is compulsory to install on the air intake pipe an 80 mm diameter terminal similar to th...

Страница 13: ...e connected to the respective G 1 2 fittings on the heating unit The mains pressure must not be more that 6 bar otherwise a pres sure reducer needs to be provided The pressure in the DHW circuit shoul...

Страница 14: ...he safety valve is not blocked Check for water leaks 3 4 2 Switching on and off For instructions on how to switch the heating unit on and off refer to the User Manual 3 4 3 Burner regulation After sta...

Страница 15: ...stem If you need to work with a single pipe unscrew the cap 2 and re move the grub screw 3 Afterwards replace the cap 2 pic 17 Important With twin tube systems before starting up the burner make sure...

Страница 16: ...air can be regulated by turning the socket screw A shown in pic 11 The setting is shown on a graduated scale B The oil pressure can be regulated by turning screw 5 in pic 17 Refer to the technical da...

Страница 17: ...e high voltage wires pic 14 pic 13 4 8 Burner ignition In the event of shutdown the red be pressed to reset The burner ignition cycle is light 7 on the control panel pic 25 summarised in the graphs in...

Страница 18: ...s pre washing proce dure and then shuts down The photoresistance is dirty Clean it The photoresistance is faulty Replace it The flame goes out or does not light Check the oil pressure Check that oil f...

Страница 19: ...ating unit to be serviced and repaired by an authorised Service Centre which can provide properly trained quali fied personnel Before carrying out any maintenance involving the replacement of componen...

Страница 20: ...solved Flow probe is faulty Flow probe is disconnected Replace it Flow probe is faulty Replace it The boiler has shut down and red light no 6 is flashing Boiler will automatically resume operation as...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...Via Cerreto 40 Tel 0365 878 31 e mail fondital fondital it www fondital it The manufacturer reserves the right to modify the data contained herein at any time without notice Uff Pubblicit Fondital IST...

Отзывы: