1.2 Operating the boiler

1.2.1 Switching on

- Open the gas stop cock.
- Turn power mains switch to ON.
- Set boiler power switch no. 17 (pic.1) to ON (the switch lights   
  up)
- Choose boiler mode through knob no. 11, no. 12 and no. 13 and  
  the programmable programmer no. 15 (please, refer to 1.2.2.3  
  and 1.2.2.4 paragraph).
- Adjust room temperature through room thermostat (when available).
- When CH is required, no. 10 light comes on (pic. 1).
- When the burner is on, no. 3 light comes on (the light comes on  

  when the flame detection electronics are powered, therefore even  

  if the light is on, flame might still not be present).

IMPORTANT
the production and maintenance of domestic hot water always 
has priority over the central heating function. When there is no 
demand for heating the boiler is kept at a temperature of 70 °C 
to avoid waitings when requiring DHW. 

1.2.2 Operation

SELECTOR (11, pic. 1)

The selector (3 positions) is for setting the operation mode of the 
unit:

 

 WINTER: all of the functions are enabled (HEATING, MAIN-

TENANCE,  DOMESTIC  WATER,  ANTI-FREEZE,  PUMP  ANTI-
BLOCKAGE).

  SUMMER:  the  HEATING  function  is  disabled  (the  functions 

MAINTENANCE, DOMESTIC WATER, ANTI-FREEZE, PUMP ANTI-
BLOCKAGE are enabled).

  ANTIFREEZE:  the  functions  ANTI-FREEZE  and  PUMP  ANTI-

BLOCKAGE are enabled.

HEATING

The control card regulates the heating temperature from a value of 
50°C to 82°C according to the value set by the operator with the 
regulator 13 (pic. 1). 
The heating function is requested when the contact of a room ther-
mostat (optional) and the contact of a programming clock (optio-
nal) are closed; such request terminates when one of the contacts 
opens or if there is a demand for hot water. 
At the end of the heating the heating pump carries out a post-cir-
culation of 180 seconds and then it turns off.
The function HEATING is not enabled when the selector is set to 
SUMMER and ANTI-FREEZE.

MAINTENANCE

In the absence of demand for heating and hot water, the control 
card will regulate the temperature of the primary at a fixed value 
of 50°C, in order to speed the response time should there be a 
demand for domestic hot water. 
The MAINTENANCE function is not enabled when the selector is in 
the ANTI-FREEZE position.

DOMESTIC HOT WATER

The  domestic  hot  water  function  starts  when  the  contact  of  the 
flow sensor closes and terminates when the same contact of the 
flow sensor opens. 
The  control  card  regulates  the  temperature  of  the  domestic  hot 
water from 35°C to 57°C depending on the setting made by the 
operator with the regulator 12 (pic. 1).
The  DOMESTIC  HOT  WATER  function  is  disabled  when  the  se-
lector is in the ANTI-FREEZE position.

ANTI-FREEZE

The  anti-freeze  function  is  enabled  in  all  of  the  positions  of  the 
selector:
- when the supply temperature falls below 5°C, the control card 
starts up the burner and the heating pump until a supply tempera-
ture of 50°C is reached, or, if the supply temperature of 50°C is not 
reached, until reaching a functioning time of 15 minutes;
- when the temperature of the domestic hot water falls below 5°C, 
the  control  card  starts  the  burner  and  the  water  pump  until  the 
temperature of 8°C of the water has been reached or, if 8°C are not 
reached, until the functioning time of 15 minutes is reached. The 
supply temperature in this phase is brought to 50°C.

HEAT ABSORPTION

When the supply temperature exceeds 90°C the pumps come on 
to absorb heat. In particular:
- in the SUMMER position the hot water pump runs until the sup-
ply temperature does not fall below 85°C;
- in the WINTER and ANTI-FREEZE position the heating pump will 
run until the supply temperature does not fall below 85°C. 

PUMP ANTI-BLOCKAGE

Every 24 hours the pumps (heating and domestic hot water) are 
activated for 180 seconds to avoid blockage.

ZONE HEATING 

Should there be the necessity to heat 2 or 3 zones indepen-
dently at a high temperature, it is possible to connect a zone 
card to the boiler (optional) + an interface Open Therm (optio-
nal). It is also possible to manage 1 zone at a high temperature 
+ 1 zone at a low temperature (with fluid temperature); in this 
case, besides these two cards, it is necessary to utilise the ex-
ternal sensors (optional) to be connected to the zone cards.

6

Содержание CAPRI C

Страница 1: ...CAPRI C IST 03 C 201 01 INSTALLATION USE AND MAINTENANCE GB...

Страница 2: ...Dear Customer Thank you for choosing and buying one of our boilers Please read these instructions carefully in order to install operate and maintain this equipment properly...

Страница 3: ...se of the packaging as all the materials can be recycled The packaging must therefore be sent to specific waste management sites Keep the packaging out of the reach of children as by its nature it may...

Страница 4: ...nnections to fuel oil mains supply page 11 3 2 5 Ventilation page 11 3 2 6 Air intake and flue gas discharge pipes page 11 3 2 7 Types and classification of air intake and flue gas discharge pipes pag...

Страница 5: ...mote control is interrupted or there are signal passage difficulties Once the connection is restored the light will turn off and the boiler will resume operation 7 Indication light red when the light...

Страница 6: ...a fixed value of 50 C in order to speed the response time should there be a demand for domestic hot water The MAINTENANCE function is not enabled when the selector is in the ANTI FREEZE position DOME...

Страница 7: ...osed as pressure increa ses boiler CH safety valve may open and water flow out Should boiler frequently shut down due to insufficient water pres sure have it serviced by an Authorized Service Centre o...

Страница 8: ...th epoxypolye ster powders Unit electronic management card Heating expansion vessel with 8 litre capacity Heating safety valve at 3 bar Three speed heating circulator Single speed domestic hot water c...

Страница 9: ...PRIORITY FLOW METER BR BURNER S2 DHW PROBE PS DHW PUMP TS LIMIT THERMOSTAT TA1 ROOM THERMOSTAT OPTIONAL 1 FLOW G 3 4 M 2 DHW G 1 2 M 3 RETURN G 3 4 M 4 COLD WATER G 1 2 M fig 3 D mm CTF 150 CTFD 120 A...

Страница 10: ...temperature setting range C 50 82 Maximum CH working pressure bar 3 3 CH expansion vessel capacity l 12 12 DHW temperature setting range C 35 57 Maximum DHW working pressure bar 6 6 DHW supply T 30K l...

Страница 11: ...elivery and return pipes Join the unit to the chimney and to the air intake pipe for D versions Connect the burner to the fuel oil supply pipes see sub section 3 2 4 Connect the unit to the power main...

Страница 12: ...ble thermal insu lation min 50 mm IMPORTANT When flue gas system is discharged through pipes diameter 125 mm it is compulsory to install on the air intake pipe an 80 mm diameter terminal similar to th...

Страница 13: ...e connected to the respective G 1 2 fittings on the heating unit The mains pressure must not be more that 6 bar otherwise a pres sure reducer needs to be provided The pressure in the DHW circuit shoul...

Страница 14: ...he safety valve is not blocked Check for water leaks 3 4 2 Switching on and off For instructions on how to switch the heating unit on and off refer to the User Manual 3 4 3 Burner regulation After sta...

Страница 15: ...stem If you need to work with a single pipe unscrew the cap 2 and re move the grub screw 3 Afterwards replace the cap 2 pic 17 Important With twin tube systems before starting up the burner make sure...

Страница 16: ...air can be regulated by turning the socket screw A shown in pic 11 The setting is shown on a graduated scale B The oil pressure can be regulated by turning screw 5 in pic 17 Refer to the technical da...

Страница 17: ...e high voltage wires pic 14 pic 13 4 8 Burner ignition In the event of shutdown the red be pressed to reset The burner ignition cycle is light 7 on the control panel pic 25 summarised in the graphs in...

Страница 18: ...s pre washing proce dure and then shuts down The photoresistance is dirty Clean it The photoresistance is faulty Replace it The flame goes out or does not light Check the oil pressure Check that oil f...

Страница 19: ...ating unit to be serviced and repaired by an authorised Service Centre which can provide properly trained quali fied personnel Before carrying out any maintenance involving the replacement of componen...

Страница 20: ...solved Flow probe is faulty Flow probe is disconnected Replace it Flow probe is faulty Replace it The boiler has shut down and red light no 6 is flashing Boiler will automatically resume operation as...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...Via Cerreto 40 Tel 0365 878 31 e mail fondital fondital it www fondital it The manufacturer reserves the right to modify the data contained herein at any time without notice Uff Pubblicit Fondital IST...

Отзывы: