7 TROUBLE-SHOOTING

UNIT STATUS

MALFUNCTION

POSSIBLE CAUSE

SOLUTIONS

The boiler is blocked, the red 
blockage light 1 is illuminated.

See paragraph
4.10. “Burner diagnostic”.

See paragraph
4.10. “Burner trouble-shooting”.

See paragraph
4.10. “Burner trouble-shooting”.

The boiler has shut down and 
red light no. 2 is on.
Reset by pressing no. 17 button.

Safety thermostat has shut the 
boiler down

Water is not flowing in the CH 
system: pipes are clogged, 
thermostatic valves are closed, 
intercepting valves in the system 
are closed

Check CH system

Pump is blocked or faulty

Check the pump

The boiler has shut down and 
red light no. 4 is flashing.
Restore correct water pressure

Insufficient water pressure

Possible water leaks

Check system for leaks

Pressure switch is disconnected Reconnect it

Water pressure switch is faulty

Replace it

The boiler has shut down, red 
light  no. 5 is  flashing.
Boiler will automatically resume 
operation as soon as the 
problem is solved

Flow probe is faulty

Flow probe is disconnected

Replace it

Flow probe is faulty

Replace it

The boiler has shut down and 
red light no. 6 is flashing.
Boiler will automatically resume 
operation as soon as the pro-
blem is solved

Boiler communication to and 
from remote control is faulty

Connecting wire is faulty

Check connecting wire

The boiler has shut down, red 
light  no. 7 is  flashing.
Boiler will automatically resume 
operation as soon as the pro-
blem is solved

Water tank is faulty

Water tank probe is discon-
nected

Reconnect it

Water tank probe is faulty

Replace it

The boiler has shut down, red 
light  no. 9 is  flashing (BTN 
model only).
Reset by pressing no. 19 button.

Flue gas thermostat is not 
consenting to boiler operation

Flue gas thermostat is faulty

Check flue gas thermostat ope-
ration: replace when faulty

Air inlet or flue gas discharge 
flow is not adequate

Replace it

Boiler is not supplying DHW

Flow meter is not operating

The system has not sufficient 
pressure or flow rate

Check DHW system

Check flow meter filter

Flow meter sensor is faulty or 
disconnected

Replace or reconnect it

Flow meter is blocked

Replace it

20

Содержание CAPRI C

Страница 1: ...CAPRI C IST 03 C 201 01 INSTALLATION USE AND MAINTENANCE GB...

Страница 2: ...Dear Customer Thank you for choosing and buying one of our boilers Please read these instructions carefully in order to install operate and maintain this equipment properly...

Страница 3: ...se of the packaging as all the materials can be recycled The packaging must therefore be sent to specific waste management sites Keep the packaging out of the reach of children as by its nature it may...

Страница 4: ...nnections to fuel oil mains supply page 11 3 2 5 Ventilation page 11 3 2 6 Air intake and flue gas discharge pipes page 11 3 2 7 Types and classification of air intake and flue gas discharge pipes pag...

Страница 5: ...mote control is interrupted or there are signal passage difficulties Once the connection is restored the light will turn off and the boiler will resume operation 7 Indication light red when the light...

Страница 6: ...a fixed value of 50 C in order to speed the response time should there be a demand for domestic hot water The MAINTENANCE function is not enabled when the selector is in the ANTI FREEZE position DOME...

Страница 7: ...osed as pressure increa ses boiler CH safety valve may open and water flow out Should boiler frequently shut down due to insufficient water pres sure have it serviced by an Authorized Service Centre o...

Страница 8: ...th epoxypolye ster powders Unit electronic management card Heating expansion vessel with 8 litre capacity Heating safety valve at 3 bar Three speed heating circulator Single speed domestic hot water c...

Страница 9: ...PRIORITY FLOW METER BR BURNER S2 DHW PROBE PS DHW PUMP TS LIMIT THERMOSTAT TA1 ROOM THERMOSTAT OPTIONAL 1 FLOW G 3 4 M 2 DHW G 1 2 M 3 RETURN G 3 4 M 4 COLD WATER G 1 2 M fig 3 D mm CTF 150 CTFD 120 A...

Страница 10: ...temperature setting range C 50 82 Maximum CH working pressure bar 3 3 CH expansion vessel capacity l 12 12 DHW temperature setting range C 35 57 Maximum DHW working pressure bar 6 6 DHW supply T 30K l...

Страница 11: ...elivery and return pipes Join the unit to the chimney and to the air intake pipe for D versions Connect the burner to the fuel oil supply pipes see sub section 3 2 4 Connect the unit to the power main...

Страница 12: ...ble thermal insu lation min 50 mm IMPORTANT When flue gas system is discharged through pipes diameter 125 mm it is compulsory to install on the air intake pipe an 80 mm diameter terminal similar to th...

Страница 13: ...e connected to the respective G 1 2 fittings on the heating unit The mains pressure must not be more that 6 bar otherwise a pres sure reducer needs to be provided The pressure in the DHW circuit shoul...

Страница 14: ...he safety valve is not blocked Check for water leaks 3 4 2 Switching on and off For instructions on how to switch the heating unit on and off refer to the User Manual 3 4 3 Burner regulation After sta...

Страница 15: ...stem If you need to work with a single pipe unscrew the cap 2 and re move the grub screw 3 Afterwards replace the cap 2 pic 17 Important With twin tube systems before starting up the burner make sure...

Страница 16: ...air can be regulated by turning the socket screw A shown in pic 11 The setting is shown on a graduated scale B The oil pressure can be regulated by turning screw 5 in pic 17 Refer to the technical da...

Страница 17: ...e high voltage wires pic 14 pic 13 4 8 Burner ignition In the event of shutdown the red be pressed to reset The burner ignition cycle is light 7 on the control panel pic 25 summarised in the graphs in...

Страница 18: ...s pre washing proce dure and then shuts down The photoresistance is dirty Clean it The photoresistance is faulty Replace it The flame goes out or does not light Check the oil pressure Check that oil f...

Страница 19: ...ating unit to be serviced and repaired by an authorised Service Centre which can provide properly trained quali fied personnel Before carrying out any maintenance involving the replacement of componen...

Страница 20: ...solved Flow probe is faulty Flow probe is disconnected Replace it Flow probe is faulty Replace it The boiler has shut down and red light no 6 is flashing Boiler will automatically resume operation as...