Operating Manual CMGZ411/421
39
13
Trouble shooting
13.1
Trouble shooting CMGZ411
Error Cause
Corrective
action
Err1
A/D-converter gets
Channel A is wrongly connected
signals < -9.7mV
(change pins z6 / z8 resp. 2 / 3)
Err2
A/D-converter gets
Channel A is wrongly connected
signals > 9.7mV
(supply and signal changed)
Short circuit in sensor connector
or sensor cable
Sensor
overloaded
Sensor with too high
sensitivity
Err5
Analog output (A+B)
Check parameter „config. output 1“
is at min. (-10V, 0/4mA)
and the offset value
Err6
Analog output value is
Check parameter „config. output 1“
„output 1 > Max.“(A+B)
and the offset value
at min. (+10V, 20mA)
13.2
Trouble shooting CMGZ421
Error Cause
Corrective
action
Err1
A/D-converter channel A
Channel A is wrongly connected
gets signals < -9.7mV
(change pins z6 / z8 resp. 2 / 3)
Err2
A/D-converter channel A
Channel A is wrongly connected
gets signals > 9.7mV
(supply and signal changed)
Short circuit in sensor connector
or sensor cable
Sensor
overloaded
Sensor with too high
sensitivity
Err3
A/D-converter channel B
Channel B is wrongly connected
gets signals < -9.7mV
(change pins d6 / d8 resp. 7 / 8)
values < -9.7mV
Err4
A/D-converter channel B
Channel B is wrongly connected
gets signals > 9.7mV
(supply and signal changed)
Short circuit in sensor connector
or sensor cable
Sensor
overloaded
Sensor with too high
sensitivity
Содержание CMGZ411
Страница 5: ...Operating Manual CMGZ411 421 5 3 3 Block Diagram CMGZ411 C411000e 3 4 Block Diagram CMGZ421 C421000e ...
Страница 9: ...Operating Manual CMGZ411 421 9 7 2 Determination of the machine configuration C400001e ...
Страница 10: ...Operating Manual CMGZ411 421 10 C400002e ...
Страница 11: ...Operating Manual CMGZ411 421 11 C400003e ...
Страница 12: ...Operating Manual CMGZ411 421 12 C400004e ...
Страница 13: ...Operating Manual CMGZ411 421 13 C400005e ...