Operating Manual CMGZ411/421
36
Linear correction at 10V CMGZ411
Purpose:
This parameter stores the factor that is used when 10V is applied to the correction input (terminals
d6 / d8). The feedback value can be changed up (>1.000) and down (<1.000). Only active if
parameter „correction input“ is „linear“.
Range:
-9.999 to
9.999
Default:
1.000
Increment:
0.001
Unit:
[-]
Gain cosine at U1, U2, U3 CMGZ411
Purpose:
Stores the value calculated with parameter „Gain cosine at U1 / U“ / U3“.
Range:
0.001 to
9.999
Default:
1.000
Increment:
0.001
Unit:
[-]
Identifier
Purpose:
This parameter identifies the CAN-BUS-Interface. Reserved for future use.
Baud rate
Purpose:
Configuration of the transmission rate of the RS-232 interface. 300, 600, 1200, 2400, 4800, 9600
baud.
Range:
300 to
9600
Default:
9600
Data bit
Purpose:
Configuration of the RS-232 interface.
Range:
7
to
8
Default:
8
Stop bit
Purpose:
Configuration of the RS-232 interface.
Range:
1
to
2
Default:
1
Parity bit
Purpose:
Configuration of the RS-232 interface.
Range:
none, odd, even
Default:
none
Содержание CMGZ411
Страница 5: ...Operating Manual CMGZ411 421 5 3 3 Block Diagram CMGZ411 C411000e 3 4 Block Diagram CMGZ421 C421000e ...
Страница 9: ...Operating Manual CMGZ411 421 9 7 2 Determination of the machine configuration C400001e ...
Страница 10: ...Operating Manual CMGZ411 421 10 C400002e ...
Страница 11: ...Operating Manual CMGZ411 421 11 C400003e ...
Страница 12: ...Operating Manual CMGZ411 421 12 C400004e ...
Страница 13: ...Operating Manual CMGZ411 421 13 C400005e ...