Table 20. Causes of OTDR Test Failures (continued)
GPU51.EPS
Top figure: Ghost after the end of the link
These are not listed in the event table and usually do
not indicate a fault in the link.
Bottom figure: Ghost in the middle of the link
Ghosts that occur in the middle of the link are listed
in the event table, along with the source of the
ghost. These can be caused by the following:
A dirty connector
A highly-reflective connector
A UP or UPC connector mated to an APC
connector
A connector that is not seated properly.
A connector that is wet with cleaning solvent.
A poorly-seated connector usually shows a large loss,
as shown in the example. A connector with the
wrong type of polish can also cause large reflections
that cause ghosts.
Ghosts caused by hidden events may not show as
ghosts in the event table.
On traces with multiple ghosts, possibly only the
strongest ghost source shows in the event table. You
can usually determine that other reflections are
ghosts because they occur at multiples of distances to
connectors and they show almost no loss. Multiple
ghosts from the same source are spaced equally
apart.
Содержание CableAnalyzer DSX-5000
Страница 24: ...xxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Страница 34: ...xxxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Страница 153: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 117 GPU70 PNG Figure 47 Twisted Pair Insertion Loss Plot...
Страница 157: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 121 GPU158 PNG Figure 50 Twisted Pair Impedance Results...
Страница 159: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 123 GPU71 PNG Figure 52 NEXT Plot...
Страница 162: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 126 GPU73 PNG Figure 55 ACR N Plot...
Страница 164: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 128 GPU106 PNG Figure 56 PS ACR N Plot...
Страница 167: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 131 GPU75 PNG Figure 58 ACR F Plot...
Страница 179: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 143 GPU92 PNG Figure 64 CMRL Plot...
Страница 182: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 146 GPU91 PNG Figure 66 CDNEXT Plot...
Страница 184: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 148 GPU78 PNG Figure 67 TCL Plot...
Страница 213: ...Chapter 5 Certify Coaxial Cabling Coaxial Autotest Results 177 GPU187 PNG Figure 81 Coaxial Impedance Results...
Страница 220: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 184...
Страница 268: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 232...
Страница 330: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 294...
Страница 338: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 302...
Страница 592: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 556...
Страница 604: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 568...
Страница 620: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 584...
Страница 669: ...Chapter 21 Specifications Display 633 GPU194 EPS Figure 213 Plug for the Headset Jack L R 3 5 mm Microphone Switch...
Страница 672: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 636...
Страница 676: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 640...
Страница 688: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 652...