Chapter 3: Certify Twisted Pair Cabling
Frequency-Domain Results
137
If the DC resistance of the wires is not the same, the DC voltage
on each wire is not the same. This causes a voltage across the
wires, which causes an offset, or bias, current in the transformer
at the far end. The offset raises or lowers the mid-point of the
transformer’s operation. If the offset is large enough, the flux
level in the transformer’s core saturates during the peaks of the
data signals. During saturation, the flux level in the core cannot
increase further in response to the change in current caused by
the data signal. Since voltage on a transformer’s output is present
only when the flux field is changing, the output voltage droops.
This causes distortion of the data signal, as shown at the bottom
of Figure 61.
Resistance unbalance within pairs can be caused by poor-quality
terminations, damaged connectors, corroded contacts, and
damaged or poorly-designed cable.
Figure 62 shows test results for resistance unbalance within pairs.
Содержание CableAnalyzer DSX-5000
Страница 24: ...xxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Страница 34: ...xxxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Страница 153: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 117 GPU70 PNG Figure 47 Twisted Pair Insertion Loss Plot...
Страница 157: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 121 GPU158 PNG Figure 50 Twisted Pair Impedance Results...
Страница 159: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 123 GPU71 PNG Figure 52 NEXT Plot...
Страница 162: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 126 GPU73 PNG Figure 55 ACR N Plot...
Страница 164: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 128 GPU106 PNG Figure 56 PS ACR N Plot...
Страница 167: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 131 GPU75 PNG Figure 58 ACR F Plot...
Страница 179: ...Chapter 3 Certify Twisted Pair Cabling Frequency Domain Results 143 GPU92 PNG Figure 64 CMRL Plot...
Страница 182: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 146 GPU91 PNG Figure 66 CDNEXT Plot...
Страница 184: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 148 GPU78 PNG Figure 67 TCL Plot...
Страница 213: ...Chapter 5 Certify Coaxial Cabling Coaxial Autotest Results 177 GPU187 PNG Figure 81 Coaxial Impedance Results...
Страница 220: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 184...
Страница 268: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 232...
Страница 330: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 294...
Страница 338: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 302...
Страница 592: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 556...
Страница 604: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 568...
Страница 620: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 584...
Страница 669: ...Chapter 21 Specifications Display 633 GPU194 EPS Figure 213 Plug for the Headset Jack L R 3 5 mm Microphone Switch...
Страница 672: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 636...
Страница 676: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 640...
Страница 688: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 652...