(8) Advanced features
Drive parameters
View the current output Hz, Amps & heat
sink temperature .
Used for diagnostic purposes in troubleshooting overheating drive .
Motor Type
(Submersible/Above Ground) Change
setting for the type of pump motor
This option in used to change the setting for the type of pump motor
the control was set to use during the initial set-up menu .
Manual run pump mode
(Off/On) Sets pump to run without
pressure switch .
Default OFF
Turn on a manual run condition at a set frequency for a defined
amount of time .
Set manual pump
frequency:
(50, 60, 70, 80 Hz)
Default 60 Hz .
Set the constant frequency (motor speed) of the Pump . (only required
if manual mode ON)
Set manual pump run time: (1/2, 1, 4, 8, 16, 24, 48, Cont .) - Hours)
Default 24 Hours .
Sets the time that the drive will run before shutting itself off . If set
for Cont . (typically not recommended), the drive will run continuously
until it is stopped manually . Broken pipe mode is not active when
manual run is on . (only required if manual mode ON)
External control mode
(Off/On) .
Default OFF .
Determines if the Alarm In contacts trips out the drive or just puts it in
Standby Mode . If Off and the contacts wired to the Alarm In terminal
blocks are inverse of the Alarm in Rely settings, the drive trips out on
External Trip . (Used for protection like over pressure .) If On and the
contacts wired to the Alarm In terminal blocks close, the drive goes to
Standby Mode . (Used for control like a timer contact for an irrigation
system .)
Alarm In Relay
(NO/NC) Sets alarm in contact settings .
Default NO .
If set to normally Open, drive will operate normally when the contacts
are open & trip (or go to standby mode) when contacts close .
(Example: An irrigation timer closes a contact to single the drive to
run, the Alarm In Relay setting should be set to NC (Normal Closed)
for the drive to be active during the irrigation cycle .)
Drive status relay
(NO/NC) Sets alarm out relay as
normally open or normally closed .
Default NO .
The state of the relay changes when the drive trips . Typically not for
use in most residential applications .
Powered by Generator
(No/Yes)
Default No .
Set the drive circuitry to expect power delivered from a gas driven
generator . Depending upon application a 5-10% pressure drop of can
be experienced when the drive is running the pump & motor at full
speed .
Ramp up sensitivity
(Switch Control Mode)
(1, 2, 3, 4, 5) Sets Ramp Up speeds .
Default 2 .
If excessive pressure fluctuations on pressure gage is noticed, the
ramp rates can be adjusted .
Ramp down sensitivity
(Switch Control Mode)
(1, 2, 3, 4, 5) Sets Ramp Down speeds
Default 2 .
If excessive pressure fluctuations on pressure gage is noticed, the
ramp rates can be adjusted .
Minimum Start-Up Time
(Switch Control Mode)
0 .5-5 Seconds
Default 1 .3
The minimum time the drive will ramp up when coming out of standby .
(9) Reset to factory defaults
Resets drive to factory defaults
Resets the drive to the initial start-up menu for drive set-up .
(10) Control Settings
(Transducer Control Mode)
Advance control settings for use with
Transducer .
Transducer Calibration
Used to calibrate transducer reading with
external pressure gage .
Enter Pressure Gauge
Reading
20-80 PSI
Adjust value to match the pressure reading of the external pressure
gauge & press enter .
PID Set Points
Adjust Transducer feedback control
parameters .
By increasing this duration time, the amount of overpressure for
drawdown can be increased . Caution: Increasing this time too much
has the potential of creating a high over pressure condition .
Set PID Control P 100-5000 Default: 400
Adjustments can change the quickness of the drive reacting to
pressure changes to reduce excessive pressure fluctuations .
Set PID Control D 1000-10000 Default: 5000
Set PID Control D 10-150 Default: 150
Pipe Fill Mode
Set Pipe Fill Time: 1-15 Minutes
Default 3 min .
Sets the time limit that pipe fill mode is active .
Pipe Fill Mode (On, Off) Fill Pipe
Default: Off
Turns On/Off Fill Pipe mode . When Pipe Fill mode is on, the drive will
not trip out on Deadhead/Low PSI fault .
Access menu options by pressing and holding edit and enter for 3 seconds .
Menu Option
Action
Notes