Flint & Walling Commander Pro Скачать руководство пользователя страница 9

Flint & Walling © Copyright 2018. All rights reserved.

  9 

(2) Maximum motor current

Set Max Motor Amps .   

Default 1 .5Hp Drive = 5 .9 A 

Default 2 .0Hp Drive = 8 .1 A 

Default 3 .0Hp Drive = 10 .9 A

Protects the pump motor assembly from operating beyond its 

maximum capability . 

(3) Maximum frequency

Options 60, 70, 80 Hz . 

Default 80 Hz .

Setting frequency determines the maximum motor speed .  For 

matched HP rating of motor & pump end, set to 60 Hz .  For pump 

end of half the HP rating of the motor (i .e . 3/4HP pump & 1 .5 HP 

motor), set to 80 Hz .

(4) Pass code enable

(Y/N) Sets 5 digit pass code using Up/

Down keys . 

Default No .

Pass code restricts parameters being changed by non-authorized 

individuals .  If pass code lost, Call 1-800-345-9422 for assistance .

(5) Underload protection

(On, Off, Prime) Turns underload 

protection on, off, or off for 30 minutes . 

Default ON .

Recommend that this is left On . Provides pump protection from 

deadhead or dry well conditions . May need to be Off/Prime when 

priming a centrifugal or if filling irrigation system .

Set Deadhead trip point:

Default 1 .5Hp Drive = 5 .0 A 

Default 2 .0Hp Drive = 6 .4 A 

Default 3 .0Hp Drive = 8 .2 A

If the motor current falls below this set point when  drive has ramped 

to maximum frequency, the drive will trip on Deadhead Fault .  Adjust 

down in increments of  .2 if experiencing nuisance deadhead trip .

Set Dry well trip point:

Default 1 .5Hp Drive = 3 .9 A 

Default 2 .0Hp Drive = 5 .3 A 

Default 3 .0Hp Drive = 6 .5 A

If the motor current falls below this set point when drive has ramped 

to maximum frequency, the drive will trip on Dry Well Fault .  Adjust 

down in increments of  .2 if experiencing nuisance dry well trip .

Set Dry well off time:

Off, 15 to 240 Min, 12 Hrs, or 24 Hrs . 

Default Off .

If set to "Off", dry well time is variable by Intelligent reset . This can be 

set to fixed time off before restarting in a range of 15 to 240 minutes 

in increments of 15 minutes, or 12 or 24 hours if desired .

(6) Bump mode  

  (Switch Control Mode)

(On, Off) Leak detection. 

Default On.

Turns On or Off a small pressure boost if the drive detects a very 

low load (leak condition).  This will reduce the run time of the 

pump and drive.

Set bump mode 

frequency:

Sets bump mode threshold frequency. 

Default 45 Hz.

When the drive is running for 15 seconds below this frequency. 

and current is below the BM current, the drive will ramp up 

for the BM duration regardless of switch state to create an 

overpressure drawdown.  

Set bump mode duration: Sets the time duration of the ramp up 

for a bump in PSI (.5 to 2.0 sec.) 

Default 0.5 sec.

By increasing this duration time, the amount of overpressure 

for drawdown can be increased.   Caution: Increasing this time 

too much has the potential of creating a high over pressure 

condition.

Set bump mode current: Sets bump mode threshold detection 

current. 

Default 1.5Hp Drive = 3.1 A 

Default 2.0Hp Drive = 4.7 A 

Default 3.0Hp Drive = 6.1 A

When the drive is running for 15 seconds below this current and 

the frequency is below the BM frequency, the drive will ramp 

up for the BM duration regardless of switch state to create an 

overpressure drawdown.  

(6) Standby Sensitivity 

   (Transducer Control Mode)

Parameters for allowing the drive go into 

standby mode at no/low flow .

Set Standby frequency:

Sets Standby threshold frequency . 

Default 45 Hz .

When the drive is running for 15 seconds below this frequency . and 

current is below the standby current, the drive will begin ramping the 

motor speed down and monitor system pressure to go into standby 

mode .  

Set Standby Drawdown:

Sets the amount the system pressure 

can fluctuate after low load is sensed 

and still go into standby mode( .5 to 2 .0 

PSI)  

Default 0 .5 PSI

By increasing this duration time, the amount of overpressure for 

drawdown can be increased .   Caution: Increasing this time too much 

has the potential of creating a high over pressure condition .

Set Standby current:

Sets Standby threshold detection 

current . 

Default 1 .5Hp Drive = 3 .1 A 

Default 2 .0Hp Drive = 4 .7 A 

Default 3 .0Hp Drive = 6 .1 A

When the drive is running for 15 seconds below this current and 

frequency is below the standby current, the drive will begin ramping 

the motor speed down and monitor system pressure to go into 

standby mode .

Set Standby rate:

Sets Standby deceleration rate (5-35) 

Default 15 .

This is the rate that the drive begins slowing down the motor to enter 

standby mode . 

(7) Broken pipe mode

(On/Off) . 

Default ON .

Turn On/Off broken pipe trip .  When On, if the drive is running the 

PMA continuously for the set time period, the drive will trip out on 

"Broken Pipe" . 

Set broken pipe run time:

(1, 8, 16, 24, 48) Hours 

Default 24 Hours .

Define the time that the drive can run continuously before tripping on 

Broke Pipe .

Access menu options by pressing and holding edit and enter for 3 seconds .

Menu Option

Action

Notes

Содержание Commander Pro

Страница 1: ... pressure Key features of the drive controller include Can use either a pressure switch no snap action or a 4 20mA transducer as the pressure control At initial power up the controller detects whether a switch or transducer is connected and automatically sets the control choice Constant water pressure with a wide range of settings 30 80 psi Note The maximum obtainable system pressure is limited by...

Страница 2: ... prevent mechanical damage which could produce serious electrical shock and or equipment failure Pump is designed to pump cold ground water that is free of air or gases Decreased pump performance and life expectancy can occur if the ground water is not cold 86ºF 30ºC or contains air or gases Pump and controls must be securely and adequately grounded as specified in section 250 43 item A of the U S...

Страница 3: ... in equipment and property damage as well as possible injury Always install a pressure relief valve capable of passing full pump flow at 100 PSI Install the pressure relief valve between the pump and pressure tank PRESSURE SETTING GUIDE System Pressure at Pressure Sensor Pressure Tank Setting PSI 2 psi 25 18 30 21 35 25 40 28 45 32 50 factory set 35 55 39 60 42 65 46 70 49 75 53 80 56 Pressure Rel...

Страница 4: ...ve access to 230V electrical supply and to the submersible motor wiring 6 Do not expose the drive to water spray greater than 30 from vertical Note Installations that require larger than 6 AWG wire will require an external junction box Run 6 AWG from the drive to the junction box and make external connections to the appropriately sized wire with wire nuts WIRING SIZING CHART Maximum Wire Lengths C...

Страница 5: ...D Black BLK Yellow YEL and W Submersible 3 Phase or 3 Wire 1 Ph motors follow colors as marked Red to RED Black to BLK Yellow YEL and Green Ground wire W Submersible 2 Wire 1 Ph motors Connect motor leads to BLK YEL and Green Ground wire W Above Ground Motor 3 Phase Only L1 to RED L2 to BLK L3 to YEL and Green Ground wire W Verify motor rotation to avoid damage to pump motor L1 L2 RED BLK YEL IN O...

Страница 6: ...ightening the thumbscrew finger tight START UP OPERATION Apply power to the controller The display should briefly show Please Wait Initializing and then read Press Enter to Begin Set Up Pressing ENTER button will begin taking you through the quick set up menu where you can select Pump type Submersible or Above Ground Motor type Three Phase 3W Single Phase if option is available Maximum Motor Curre...

Страница 7: ...imer low level switch etc can be used to trip the drive with an External Fault trip For this connection to work properly the Alarm in Relay contact condition setting in the Advanced Features Menu must be set to match the switch position to activate the drive Example An irrigation timer closes a contact to single the drive to run the Alarm In Relay setting should be set to NC Normal Closed for the ...

Страница 8: ...eter press the EDIT button followed by the UP and DOWN buttons to set or choose the new value Once the new values is set press the ENTER button to accept the new value or the ESCAPE button to discard the change Once you are done viewing and changing the parameters press ESCAPE to return to the home screen For further information to change these parameters please call Technical Support at 800 742 5...

Страница 9: ...w the BM current the drive will ramp up for the BM duration regardless of switch state to create an overpressure drawdown Set bump mode duration Sets the time duration of the ramp up for a bump in PSI 5 to 2 0 sec Default 0 5 sec By increasing this duration time the amount of overpressure for drawdown can be increased Caution Increasing this time too much has the potential of creating a high over ...

Страница 10: ...n or normally closed Default NO The state of the relay changes when the drive trips Typically not for use in most residential applications Powered by Generator No Yes Default No Set the drive circuitry to expect power delivered from a gas driven generator Depending upon application a 5 10 pressure drop of can be experienced when the drive is running the pump motor at full speed Ramp up sensitivity...

Страница 11: ...uit Replace transducer Deadhead Switch control Pump running against a closed discharge Make sure that there is not a valve closed or obstruction between the pump and pressure switch Damaged or clogged pressure switch Check continuity across switch contacts without wire connected and replace and or clean pressure port Deadhead sensitivity incorrect Adjust deadhead sensitivity in Underload Protectio...

Страница 12: ...ith higher flow rating if head requirement is still satisfied Temperature in the controller is too high If the controller s heat exchanger becomes too hot the controller will reduce the output frequency to the motor to lower the power consumption Make sure there is at least 4 inches of room around the controller for movement of air Avoid direct sunlight Reduce ambient temperature below 104 F 40 C ...

Отзывы: