background image

Flint & Walling © Copyright 2018. All rights reserved.

  4 

CONTROLLER LOCATION SELECTION

The NEMA 3R controller is intended for indoor and outdoor 

use and for operation in ambient temperatures up to 125° 

F (50° C) . It should be mounted in a location that provides 

protection from water sprays greater than 30° from vertical . 

The drive should only be accessed by trained and authorized 

personnel . To ensure maximum weather protection, the 

unit must be mounted vertically with the cover properly 

aligned and secured with all lid screws . The following 

recommendations will help in selection of the proper location 

of the unit:
1 .  A  tank tee is recommended for mounting the tank, 

pressure switch/transducer, pressure gauge, and 

pressure relief valve at one junction . If a tank tee is not 

used, the pressure switch/transducer should be located 

within 6 ft . (1 .8 meters) of the pressure tank to minimize 

pressure fluctuations . There should be no elbows 

between the tank and pressure switch/transducer .

2 .  The unit should be mounted on a sturdy supporting 

structure such as a wall or supporting post - please 

account for the fact that the unit weighs approximately 20 

lbs .

3 .  The electronics inside the controller are air-cooled . As a 

result, there should be at least 6 inches of clearance on 

each side and below the unit to allow room for air flow .

IL1721

Commander

®

 Pro

Variable Speed

Controller

®

FW1629 A

COMMANDER

®

 PRO

Variable Frequency Drive

www.getcommanderpro.com

FW1629 B

6.8366

2.7963

Notes do not print

Pressure

Tank

Pressure

Switch or

Transducer

Pump

Motor

Pressure 

Relief Valve

Figure 2 Location Diagram

There should be at least 6 inches of 

clearance on each side and below the unit to allow room 

for proper air flow. There are to be no elbows between 

the tank and pressure switch.

4 .  The controller should only be mounted with the wiring 

end oriented downward . If possible for best cooling, 

the controller should not be placed in direct sunlight 

or other locations subject to extreme temperatures or 

humidity (mounting location should not be subjected to 

condensation) .

5 .  The mounting location should have access to 230V  

electrical supply and to the submersible motor wiring .

6 .  Do not expose the drive to water spray greater than 30° 

from vertical .

Note: Installations that require larger than 6 AWG wire will 

require an external junction box . Run 6 AWG from the drive 

to the junction box and make external connections to the 

appropriately sized wire with wire nuts .

WIRING SIZING CHART

Maximum Wire Lengths Connecting the Controller  

to The Main Circuit Box 

(Based On 3% Voltage Drop At 230V)

Motor 

HP

Copper 

Wire 

Size 

(AWG)

14

12

10

8

6

4

3

2

Circuit 

Breaker

1 .5/2

Max . 

Length . 

(Ft .)

85* 140* 220 345 550 680 895 20 AMP

3

115* 180 285 455 560 740 25 AMP

5

115 185 290 360 470 40 AMP

* Wire with 90°C Insulation only

PUMP WIRING

If submersible pump type is chosen, the output of the drive is 

3-phase .  (If the option is available, 3-wire may be available 

for submersible pumps) . 
The power output terminals (for motor wire connections) are 

located on the lower right-hand side of the controller and are 

labeled RED, BLK, YEL and (

W

) . To select the wire size refer 

to the pump owner’s manual, NEC and local codes for proper 

wire size . 
NOTICE: Regardless of owner’s manual, wire length should 

not exceed 1000 ft . 
If the Commander Pro Controller is used with above ground 

motors the output is limited to 3-phase .  To maximize motor 

life the cable length between the controller and the motor 

should be limited to a maximum length of 25 ft .  Refer to the 

pump owner’s manual, NEC and local codes for proper wire 

size .  Caution: Correct motor rotating needs to be verified to 

avoid pump and motor damage . 

  Due to the inherent voltage changing 

characteristics of variable frequency drives (VFD), there 

is additional stress placed on the insulation of the wire 

between the controller and the motor compared to a 

standard pump system. Extra care must be taken when 

using Un-jacketed Flat Parallel Pump Cable to ensure that 

the insulation on each of the separated wires is the same 

thickness. Care must also be taken to ensure a proper 

seal with shrink tubing on any splices. Failure to take 

these precautions can lead to “wire burn through” that 

will shut down the system. Under these circumstances, 

no permanent damage usually occurs to the controller or 

motor. For further details call Technical Support at  

800-742-5044.

SEPARATED WIRE

Содержание Commander Pro

Страница 1: ... pressure Key features of the drive controller include Can use either a pressure switch no snap action or a 4 20mA transducer as the pressure control At initial power up the controller detects whether a switch or transducer is connected and automatically sets the control choice Constant water pressure with a wide range of settings 30 80 psi Note The maximum obtainable system pressure is limited by...

Страница 2: ... prevent mechanical damage which could produce serious electrical shock and or equipment failure Pump is designed to pump cold ground water that is free of air or gases Decreased pump performance and life expectancy can occur if the ground water is not cold 86ºF 30ºC or contains air or gases Pump and controls must be securely and adequately grounded as specified in section 250 43 item A of the U S...

Страница 3: ... in equipment and property damage as well as possible injury Always install a pressure relief valve capable of passing full pump flow at 100 PSI Install the pressure relief valve between the pump and pressure tank PRESSURE SETTING GUIDE System Pressure at Pressure Sensor Pressure Tank Setting PSI 2 psi 25 18 30 21 35 25 40 28 45 32 50 factory set 35 55 39 60 42 65 46 70 49 75 53 80 56 Pressure Rel...

Страница 4: ...ve access to 230V electrical supply and to the submersible motor wiring 6 Do not expose the drive to water spray greater than 30 from vertical Note Installations that require larger than 6 AWG wire will require an external junction box Run 6 AWG from the drive to the junction box and make external connections to the appropriately sized wire with wire nuts WIRING SIZING CHART Maximum Wire Lengths C...

Страница 5: ...D Black BLK Yellow YEL and W Submersible 3 Phase or 3 Wire 1 Ph motors follow colors as marked Red to RED Black to BLK Yellow YEL and Green Ground wire W Submersible 2 Wire 1 Ph motors Connect motor leads to BLK YEL and Green Ground wire W Above Ground Motor 3 Phase Only L1 to RED L2 to BLK L3 to YEL and Green Ground wire W Verify motor rotation to avoid damage to pump motor L1 L2 RED BLK YEL IN O...

Страница 6: ...ightening the thumbscrew finger tight START UP OPERATION Apply power to the controller The display should briefly show Please Wait Initializing and then read Press Enter to Begin Set Up Pressing ENTER button will begin taking you through the quick set up menu where you can select Pump type Submersible or Above Ground Motor type Three Phase 3W Single Phase if option is available Maximum Motor Curre...

Страница 7: ...imer low level switch etc can be used to trip the drive with an External Fault trip For this connection to work properly the Alarm in Relay contact condition setting in the Advanced Features Menu must be set to match the switch position to activate the drive Example An irrigation timer closes a contact to single the drive to run the Alarm In Relay setting should be set to NC Normal Closed for the ...

Страница 8: ...eter press the EDIT button followed by the UP and DOWN buttons to set or choose the new value Once the new values is set press the ENTER button to accept the new value or the ESCAPE button to discard the change Once you are done viewing and changing the parameters press ESCAPE to return to the home screen For further information to change these parameters please call Technical Support at 800 742 5...

Страница 9: ...w the BM current the drive will ramp up for the BM duration regardless of switch state to create an overpressure drawdown Set bump mode duration Sets the time duration of the ramp up for a bump in PSI 5 to 2 0 sec Default 0 5 sec By increasing this duration time the amount of overpressure for drawdown can be increased Caution Increasing this time too much has the potential of creating a high over ...

Страница 10: ...n or normally closed Default NO The state of the relay changes when the drive trips Typically not for use in most residential applications Powered by Generator No Yes Default No Set the drive circuitry to expect power delivered from a gas driven generator Depending upon application a 5 10 pressure drop of can be experienced when the drive is running the pump motor at full speed Ramp up sensitivity...

Страница 11: ...uit Replace transducer Deadhead Switch control Pump running against a closed discharge Make sure that there is not a valve closed or obstruction between the pump and pressure switch Damaged or clogged pressure switch Check continuity across switch contacts without wire connected and replace and or clean pressure port Deadhead sensitivity incorrect Adjust deadhead sensitivity in Underload Protectio...

Страница 12: ...ith higher flow rating if head requirement is still satisfied Temperature in the controller is too high If the controller s heat exchanger becomes too hot the controller will reduce the output frequency to the motor to lower the power consumption Make sure there is at least 4 inches of room around the controller for movement of air Avoid direct sunlight Reduce ambient temperature below 104 F 40 C ...

Отзывы: