background image

Flint & Walling © Copyright 2018. All rights reserved.

  12 

TVS/VS15

TVS/VS20

TVS/VS30

TVS50

Input from 

Power 

Source 

(single 

phase)

Voltage

180 -264 AC

180 -264 AC

180 -264 AC

180 -264 AC

Frequency

48 - 62 Hz

48 - 62 Hz

48 - 62 Hz

48 - 62 Hz

Current (max)

14 .5 Amps RMS 1ø 

19 Amps RMS 1ø 

23 Amps RMS 1ø 

36 Amps RMS 1ø

Power Factor

1 .0 (constant)

1 .0 (constant)

1 .0 (constant)

1 .0 (constant)

Output to 

Motor (three-

phase)

Voltage

Adjusts with Frequency

Adjusts with Frequency

Adjusts with Frequency

Adjusts with Frequency

Frequency Range 

30 - 80 Hz

Current Factory 

Programmed

5 .9 amps (RMS, each 

phase)

8 .1 amps (RMS, each 

phase)

10 .9 amps (RMS, each 

phase)

18 .0 amps (RMS, each 

phase)

Current (max)

6 .5 amps (RMS, each 

phase)

8 .5 amps (RMS, each 

phase)

10 .9 amps (RMS, each 

phase)

18 .0 amps (RMS, each 

phase)

Pressure 

Setting

Factory preset

50 PSI

Adjustment range

30 - 80 PSI switch / 15 - 95 PSI transducer

Operating 

Conditions

Temperature (at 230 

VAC input)

-20° to 50°C (-4° to 125°F)

Relative Humidity

Max 95% Non-condensing

Controller 

Size

NEMA 3R (Indoor/

Outdoor) 

17” H x 9 .25” W x 5 .25” D

19" H X 9 .75" W X 5 .25" 

D

Weight

19 lbs .

25 lbs .

Minimum generator sizing

4 .8kW

8 .0kW

10 .0kW

15 .7kW

SYSTEM TROUBLESHOOTING GUIDE

SYMPTOM

POSSIBLE CAUSE

CORRECTIVE ACTION

Water flow rate is not as 

high as expected .

Motor/Pump is running backwards .

Switch two of the three wires leading from the controller to the 

3-phase motor .

Pump capacity cannot supply the demand .

Use pump with higher flow rating (if head requirement is still 

satisfied) .

Temperature in the controller is too high . If the 

controller’s heat exchanger becomes too hot, 

the controller will reduce the output frequency 

to the motor to lower the power consumption .

Make sure there is at least 4 inches of room around the controller for 

movement of air . Avoid direct sunlight . Reduce ambient temperature 

below 104°F (40°C) . Increase input voltage if below 230 VAC .

Pump capacity cannot supply the demand . 

Use pump with higher flow rating (if head requirement is still 

satisfied) . 

Excessive pressure 

fluctuations .

Waterlogged tank .

Check tank for bladder damage . Replace if necessary .
Reset the tank pre-charge pressure (should be 70% of pressure 

switch/transducer setting) .

Pressure tank is too small for flow rating of the 

pump .

Use larger tank (4 gal . tank minimum) .

Motor runs continuously 

with no flow demand .

Leak in the household or outdoor plumbing .

Check for leaky faucets, valves and/or pipe fittings and repair .

Leak in the pitless adapter .

Re-seat the pitless adapter . Replace seal as needed .

Drive will not come out of 

standby mode

Bad pressure switch

Check continuity across pressure switch terminals and replace if 

necessary

Loose pressure switch wire connection or 

broken wire

Check pressure switch wire connections on display board and at 

pressure switch . Check wire for continuity .

Drive is in switch control mode and transducer 

is  hooked up backwards .

Check to ensure transducer brown lead is connected to S1 and blue 

lead is connected to S2 terminals . Change control mode from switch 

to transducer .

DRIVE SPECIFICATIONS

Содержание Commander Pro

Страница 1: ... pressure Key features of the drive controller include Can use either a pressure switch no snap action or a 4 20mA transducer as the pressure control At initial power up the controller detects whether a switch or transducer is connected and automatically sets the control choice Constant water pressure with a wide range of settings 30 80 psi Note The maximum obtainable system pressure is limited by...

Страница 2: ... prevent mechanical damage which could produce serious electrical shock and or equipment failure Pump is designed to pump cold ground water that is free of air or gases Decreased pump performance and life expectancy can occur if the ground water is not cold 86ºF 30ºC or contains air or gases Pump and controls must be securely and adequately grounded as specified in section 250 43 item A of the U S...

Страница 3: ... in equipment and property damage as well as possible injury Always install a pressure relief valve capable of passing full pump flow at 100 PSI Install the pressure relief valve between the pump and pressure tank PRESSURE SETTING GUIDE System Pressure at Pressure Sensor Pressure Tank Setting PSI 2 psi 25 18 30 21 35 25 40 28 45 32 50 factory set 35 55 39 60 42 65 46 70 49 75 53 80 56 Pressure Rel...

Страница 4: ...ve access to 230V electrical supply and to the submersible motor wiring 6 Do not expose the drive to water spray greater than 30 from vertical Note Installations that require larger than 6 AWG wire will require an external junction box Run 6 AWG from the drive to the junction box and make external connections to the appropriately sized wire with wire nuts WIRING SIZING CHART Maximum Wire Lengths C...

Страница 5: ...D Black BLK Yellow YEL and W Submersible 3 Phase or 3 Wire 1 Ph motors follow colors as marked Red to RED Black to BLK Yellow YEL and Green Ground wire W Submersible 2 Wire 1 Ph motors Connect motor leads to BLK YEL and Green Ground wire W Above Ground Motor 3 Phase Only L1 to RED L2 to BLK L3 to YEL and Green Ground wire W Verify motor rotation to avoid damage to pump motor L1 L2 RED BLK YEL IN O...

Страница 6: ...ightening the thumbscrew finger tight START UP OPERATION Apply power to the controller The display should briefly show Please Wait Initializing and then read Press Enter to Begin Set Up Pressing ENTER button will begin taking you through the quick set up menu where you can select Pump type Submersible or Above Ground Motor type Three Phase 3W Single Phase if option is available Maximum Motor Curre...

Страница 7: ...imer low level switch etc can be used to trip the drive with an External Fault trip For this connection to work properly the Alarm in Relay contact condition setting in the Advanced Features Menu must be set to match the switch position to activate the drive Example An irrigation timer closes a contact to single the drive to run the Alarm In Relay setting should be set to NC Normal Closed for the ...

Страница 8: ...eter press the EDIT button followed by the UP and DOWN buttons to set or choose the new value Once the new values is set press the ENTER button to accept the new value or the ESCAPE button to discard the change Once you are done viewing and changing the parameters press ESCAPE to return to the home screen For further information to change these parameters please call Technical Support at 800 742 5...

Страница 9: ...w the BM current the drive will ramp up for the BM duration regardless of switch state to create an overpressure drawdown Set bump mode duration Sets the time duration of the ramp up for a bump in PSI 5 to 2 0 sec Default 0 5 sec By increasing this duration time the amount of overpressure for drawdown can be increased Caution Increasing this time too much has the potential of creating a high over ...

Страница 10: ...n or normally closed Default NO The state of the relay changes when the drive trips Typically not for use in most residential applications Powered by Generator No Yes Default No Set the drive circuitry to expect power delivered from a gas driven generator Depending upon application a 5 10 pressure drop of can be experienced when the drive is running the pump motor at full speed Ramp up sensitivity...

Страница 11: ...uit Replace transducer Deadhead Switch control Pump running against a closed discharge Make sure that there is not a valve closed or obstruction between the pump and pressure switch Damaged or clogged pressure switch Check continuity across switch contacts without wire connected and replace and or clean pressure port Deadhead sensitivity incorrect Adjust deadhead sensitivity in Underload Protectio...

Страница 12: ...ith higher flow rating if head requirement is still satisfied Temperature in the controller is too high If the controller s heat exchanger becomes too hot the controller will reduce the output frequency to the motor to lower the power consumption Make sure there is at least 4 inches of room around the controller for movement of air Avoid direct sunlight Reduce ambient temperature below 104 F 40 C ...

Отзывы: