background image

Flint & Walling © Copyright 2018. All rights reserved.

  7 

Underload Sensitivity

The controller is configured at the factory to ensure detection 

of Underload faults in a wide variety of pumping applications 

including dead head and run dry conditions . In very rare 

cases (as with certain pumps in shallow wells) this trip level 

may result in nuisance faults . If the pump is installed in a 

shallow well, activate the controller and observe system 

behavior . Once the controller begins to regulate pressure, 

check operation at several flow rates to make sure the default 

sensitivity does not induce nuisance Underload trips . If it 

becomes necessary to desensitize the Underload trip level, 

please call of Technical Support at 800-742-5044 for further 

details . 

UNDERLOAD INTELLIGENT RESET 

(Display shows Dry Well Trip)

If a motor Underload fault condition occurs, the most likely 

cause is an over-pumped well (dry well) or loss of incoming 

feed water to the pump . In a dry well situation to allow 

the well to recover, the controller will wait 30 seconds to 5 

minutes, determined by the amount of time the motor had 

been running before sensing the dry well, before restarting 

the motor . For example, the first time the fault occurs and 

the pump has been running 6 minutes, the controller stop the 

motor and will wait 30 seconds before attempting to restart 

the pump . If the system would then run for 2 minutes and an 

dry well fault recurs, the controller will wait 3 minutes before 

attempting to restart the pump . This schedule allows for the 

minimum off-time possible based on the recovery time of the 

well .
If there is an obstruction (such as a closed valve) between 

the pump and the pressure switch/transducer, the controller 

will also sense an underload deadhead condition stopping the 

motor to avoid damaging the pump .

0

1

2

3

4

5

6

0

1

2

3

4

5

6

7

8

IL1448

Run Time (Minutes)

O

ff

 T

im

(M

in

ut

es

)

“Intelligent Reset” Recovery Time

Over Temperature Protection

The controller is designed for full power operation in ambient 

temperatures to up to 125°F (50°C) as long as the input 

voltage is at 230V .  Under severe thermal situations, the 

controller will reduce power output by reducing the output 

frequency in order to avoid shutting down .  Full speed output 

is restored when the temperature cools .

External alarm trip terminals

The control is fitted with an Alarm In terminal block on the 

display board . Using these terminals, an external control 

switch can be wired to the drive .  With this connection, an 

external control such as an over pressure, under pressure, 

timer, low level switch, etc . can be used to trip the drive with 

an “External Fault” trip .  For this connection to work properly, 

the Alarm in Relay contact condition setting in the Advanced 

Features Menu must be set to match the switch position 

to activate the drive . (Example: An irrigation timer closes a 

contact to single the drive to run, the Alarm In Relay setting 

should be set to NC (Normal Closed) for the drive to be active 

during the irrigation cycle .) 
This connection can also be used with the “External Control” 

feature in the advanced options menu to put the drive in 

standby rather than causing an external fault trip .

Caution: The external control must be a dry contact 

(i.e. no voltage applied to the Alarm In terminals of the 

controller) to not damage the drive circuit boards.  An 

external control with voltage can only be used with the 

controller if an isolation relay is used in conjunction with 

the voltage source. Contact technical support for more 

information.
Leaky Systems (Pressure Switch Control)

Leaky water systems might keep the controller running due 

to the accurate pressure sensing capability of the pressure 

switch . Continuous running or starts and stops do not hurt 

the controller, pump or motor . However, to reduce the on-time 

of the controller/pump/motor, a “Bump-Mode” has been 

programmed into the drive . During very low flow (or leaky) 

conditions this feature periodically increases the speed of the 

pump several PSI above the set point and shuts off the pump . 

This adds some time to bleed off before the system starts 

up again . This “Bump-Mode” can be turned off or adjusted if 

desired . Please call Technical Support at 800-742-5044 for 

further details . 

Fill Pipe Mode (Transducer Control)

At initial power up, the drive is automatically in the Fill Pipe 

Mode for 3 minutes .  This allows a new installed system to 

fill the pip and build up pressure without having the pump 

trip out because it is sensing low pressure .  If additional time 

is needed, this mode can be turned back on and the time 

increased in Parameter menu #7 .

Use of Engine Drive Generators

There are several technical issues that go into correct sizing 

of a generator for use with a VFD controller . Since the VFD 

is a “non-linear load”, the generator needs to be oversized 

considerably for proper operation . Listed below is minimum 

recommended sizing of a generator for each drive rating if the 

VFD controller is the only load on the generator . Because of 

the variation in design of voltage controls used in generators, 

the generator manufacture should always be contacted to 

verify the correct sizing when used with a VFD controller . 

For best results when used with a generator in the Advanced 

Features Menu the 

Powered by Generator option needs to 

be set to “Yes”. 

Содержание Commander Pro

Страница 1: ... pressure Key features of the drive controller include Can use either a pressure switch no snap action or a 4 20mA transducer as the pressure control At initial power up the controller detects whether a switch or transducer is connected and automatically sets the control choice Constant water pressure with a wide range of settings 30 80 psi Note The maximum obtainable system pressure is limited by...

Страница 2: ... prevent mechanical damage which could produce serious electrical shock and or equipment failure Pump is designed to pump cold ground water that is free of air or gases Decreased pump performance and life expectancy can occur if the ground water is not cold 86ºF 30ºC or contains air or gases Pump and controls must be securely and adequately grounded as specified in section 250 43 item A of the U S...

Страница 3: ... in equipment and property damage as well as possible injury Always install a pressure relief valve capable of passing full pump flow at 100 PSI Install the pressure relief valve between the pump and pressure tank PRESSURE SETTING GUIDE System Pressure at Pressure Sensor Pressure Tank Setting PSI 2 psi 25 18 30 21 35 25 40 28 45 32 50 factory set 35 55 39 60 42 65 46 70 49 75 53 80 56 Pressure Rel...

Страница 4: ...ve access to 230V electrical supply and to the submersible motor wiring 6 Do not expose the drive to water spray greater than 30 from vertical Note Installations that require larger than 6 AWG wire will require an external junction box Run 6 AWG from the drive to the junction box and make external connections to the appropriately sized wire with wire nuts WIRING SIZING CHART Maximum Wire Lengths C...

Страница 5: ...D Black BLK Yellow YEL and W Submersible 3 Phase or 3 Wire 1 Ph motors follow colors as marked Red to RED Black to BLK Yellow YEL and Green Ground wire W Submersible 2 Wire 1 Ph motors Connect motor leads to BLK YEL and Green Ground wire W Above Ground Motor 3 Phase Only L1 to RED L2 to BLK L3 to YEL and Green Ground wire W Verify motor rotation to avoid damage to pump motor L1 L2 RED BLK YEL IN O...

Страница 6: ...ightening the thumbscrew finger tight START UP OPERATION Apply power to the controller The display should briefly show Please Wait Initializing and then read Press Enter to Begin Set Up Pressing ENTER button will begin taking you through the quick set up menu where you can select Pump type Submersible or Above Ground Motor type Three Phase 3W Single Phase if option is available Maximum Motor Curre...

Страница 7: ...imer low level switch etc can be used to trip the drive with an External Fault trip For this connection to work properly the Alarm in Relay contact condition setting in the Advanced Features Menu must be set to match the switch position to activate the drive Example An irrigation timer closes a contact to single the drive to run the Alarm In Relay setting should be set to NC Normal Closed for the ...

Страница 8: ...eter press the EDIT button followed by the UP and DOWN buttons to set or choose the new value Once the new values is set press the ENTER button to accept the new value or the ESCAPE button to discard the change Once you are done viewing and changing the parameters press ESCAPE to return to the home screen For further information to change these parameters please call Technical Support at 800 742 5...

Страница 9: ...w the BM current the drive will ramp up for the BM duration regardless of switch state to create an overpressure drawdown Set bump mode duration Sets the time duration of the ramp up for a bump in PSI 5 to 2 0 sec Default 0 5 sec By increasing this duration time the amount of overpressure for drawdown can be increased Caution Increasing this time too much has the potential of creating a high over ...

Страница 10: ...n or normally closed Default NO The state of the relay changes when the drive trips Typically not for use in most residential applications Powered by Generator No Yes Default No Set the drive circuitry to expect power delivered from a gas driven generator Depending upon application a 5 10 pressure drop of can be experienced when the drive is running the pump motor at full speed Ramp up sensitivity...

Страница 11: ...uit Replace transducer Deadhead Switch control Pump running against a closed discharge Make sure that there is not a valve closed or obstruction between the pump and pressure switch Damaged or clogged pressure switch Check continuity across switch contacts without wire connected and replace and or clean pressure port Deadhead sensitivity incorrect Adjust deadhead sensitivity in Underload Protectio...

Страница 12: ...ith higher flow rating if head requirement is still satisfied Temperature in the controller is too high If the controller s heat exchanger becomes too hot the controller will reduce the output frequency to the motor to lower the power consumption Make sure there is at least 4 inches of room around the controller for movement of air Avoid direct sunlight Reduce ambient temperature below 104 F 40 C ...

Отзывы: