Flint & Walling Commander Pro Скачать руководство пользователя страница 3

Flint & Walling © Copyright 2018. All rights reserved.

  3 

SYSTEM COMPONENTS

Please be sure that you have all major system components 

necessary to properly install the submersible pump system . 

Other components may also be necessary depending on the 

application requirements .
1 .  Submersible pump end
2 .  Submersible motor
3 .  Variable speed controller
4 .  Pressure tank
5 .  Pressure switch or transducer (packaged with controller)
6 .  Pressure relief valve  (purchased separately)
7 .  Pressure gauge  (purchased separately)

PIPING

General Information

The system is capable of flows up to 40 GPM . Discharge 

piping is recommended to be 1 .25” for installations in which 

flows will exceed 12 GPM . The use of smaller pipe will 

increase friction losses and can severely limit the maximum 

capacity of the system .
This pump may be capable of pressures exceeding 325 PSI 

under maximum conditions, select pipe accordingly . Consult 

your pipe supplier to determine the best pipe material for the 

installation

Pump Inspection

Prior to installation check the pump, motor, controller and tank 

for shipment damage . 

Pressure Tank 

The Air-E-Tainer® tank supplied with your system has a 

factory set pre-charge of 35 PSI . Installer must recheck to 

make sure tank is still 35 PSI . This is 70% of the factory 

preset operating pressure of 50 PSI . Any change in operating 

system pressure will require that the pre charge in the tank 

be modified to 70% of that pressure . See Tank Table for 

minimum pressure tank size .

MINIMUM PRESSURE TANK SIZE (TOTAL 

CAPACITY)

Controller

Pump Flow 

Rating less 

than 12 GPM

Pump Flow 

Rating 12 GPM or 

higher

VS15/TVS15

4 .6 Gal (132477)

4 .6 Gal (132477)

VS20/TVS20

4 .6 Gal (132477)

14 Gal (132661)

VS30/TVS30

14 Gal (132661)

14 Gal (132661)

TVS50

14 Gal (132661)

20 Gal (132662)

 Many pumps can develop excessive 

pressure, resulting in equipment and property damage 

as well as possible injury. Always install a pressure relief 

valve capable of passing full pump flow at 100 PSI. Install 

the pressure relief valve between the pump and pressure 

tank.

PRESSURE SETTING GUIDE

System Pressure  

(at Pressure Sensor)

Pressure Tank Setting 

(PSI) (+/- 2 psi)

25

18

30

21

35

25

40

28

45

32

50 (factory set)

35

55

39

60

42

65

46

70

49

75

53

80

56

Pressure Relief Valve

The pressure relief valve  and the discharge outlet need a 

flow rating which exceeds the flow capacity of the installation 

at the relief pressure . When located in an area where a water 

leak or relief valve blow-off may damage property connect 

an adequate drain line to the pressure relief valve . Run the 

line to a suitable drain or to an area where the water will not 

damage property . 

 Not providing an adequate relief valve 

can cause extreme overpressure which could result in 

personal and/or property damage. It is recommended 

that you manually activate the valve monthly to keep it in 

good working order.

Discharge Pipe

When discharge piping requires an adapter it is 

recommended that a stainless steel adapter be used . 

Galvanized fittings or pipe should not be connected directly 

to the stainless steel discharge head of the pump as galvanic 

corrosion may occur . Barb type connectors should always 

be double clamped . Torque arrestors are not required on this 

installation due to the soft starting characteristics of the motor 

and controller

Check Valve

A check valve is factory installed in the discharge head of the 

submersible pump . This maintains water within the pipe when 

the pump is not operating . For well depths exceeding 100 

feet, an additional check valve should be installed every 100 

feet .

Safety Rope

A safety rope eyelet is provided at the discharge of the pump . 

It is recommended to attach a nylon safety rope . This will 

assist in the removal of the pump and also prevent loss of 

the unit in the bottom of the well due to a loose fitting or pipe 

deterioration .

Содержание Commander Pro

Страница 1: ... pressure Key features of the drive controller include Can use either a pressure switch no snap action or a 4 20mA transducer as the pressure control At initial power up the controller detects whether a switch or transducer is connected and automatically sets the control choice Constant water pressure with a wide range of settings 30 80 psi Note The maximum obtainable system pressure is limited by...

Страница 2: ... prevent mechanical damage which could produce serious electrical shock and or equipment failure Pump is designed to pump cold ground water that is free of air or gases Decreased pump performance and life expectancy can occur if the ground water is not cold 86ºF 30ºC or contains air or gases Pump and controls must be securely and adequately grounded as specified in section 250 43 item A of the U S...

Страница 3: ... in equipment and property damage as well as possible injury Always install a pressure relief valve capable of passing full pump flow at 100 PSI Install the pressure relief valve between the pump and pressure tank PRESSURE SETTING GUIDE System Pressure at Pressure Sensor Pressure Tank Setting PSI 2 psi 25 18 30 21 35 25 40 28 45 32 50 factory set 35 55 39 60 42 65 46 70 49 75 53 80 56 Pressure Rel...

Страница 4: ...ve access to 230V electrical supply and to the submersible motor wiring 6 Do not expose the drive to water spray greater than 30 from vertical Note Installations that require larger than 6 AWG wire will require an external junction box Run 6 AWG from the drive to the junction box and make external connections to the appropriately sized wire with wire nuts WIRING SIZING CHART Maximum Wire Lengths C...

Страница 5: ...D Black BLK Yellow YEL and W Submersible 3 Phase or 3 Wire 1 Ph motors follow colors as marked Red to RED Black to BLK Yellow YEL and Green Ground wire W Submersible 2 Wire 1 Ph motors Connect motor leads to BLK YEL and Green Ground wire W Above Ground Motor 3 Phase Only L1 to RED L2 to BLK L3 to YEL and Green Ground wire W Verify motor rotation to avoid damage to pump motor L1 L2 RED BLK YEL IN O...

Страница 6: ...ightening the thumbscrew finger tight START UP OPERATION Apply power to the controller The display should briefly show Please Wait Initializing and then read Press Enter to Begin Set Up Pressing ENTER button will begin taking you through the quick set up menu where you can select Pump type Submersible or Above Ground Motor type Three Phase 3W Single Phase if option is available Maximum Motor Curre...

Страница 7: ...imer low level switch etc can be used to trip the drive with an External Fault trip For this connection to work properly the Alarm in Relay contact condition setting in the Advanced Features Menu must be set to match the switch position to activate the drive Example An irrigation timer closes a contact to single the drive to run the Alarm In Relay setting should be set to NC Normal Closed for the ...

Страница 8: ...eter press the EDIT button followed by the UP and DOWN buttons to set or choose the new value Once the new values is set press the ENTER button to accept the new value or the ESCAPE button to discard the change Once you are done viewing and changing the parameters press ESCAPE to return to the home screen For further information to change these parameters please call Technical Support at 800 742 5...

Страница 9: ...w the BM current the drive will ramp up for the BM duration regardless of switch state to create an overpressure drawdown Set bump mode duration Sets the time duration of the ramp up for a bump in PSI 5 to 2 0 sec Default 0 5 sec By increasing this duration time the amount of overpressure for drawdown can be increased Caution Increasing this time too much has the potential of creating a high over ...

Страница 10: ...n or normally closed Default NO The state of the relay changes when the drive trips Typically not for use in most residential applications Powered by Generator No Yes Default No Set the drive circuitry to expect power delivered from a gas driven generator Depending upon application a 5 10 pressure drop of can be experienced when the drive is running the pump motor at full speed Ramp up sensitivity...

Страница 11: ...uit Replace transducer Deadhead Switch control Pump running against a closed discharge Make sure that there is not a valve closed or obstruction between the pump and pressure switch Damaged or clogged pressure switch Check continuity across switch contacts without wire connected and replace and or clean pressure port Deadhead sensitivity incorrect Adjust deadhead sensitivity in Underload Protectio...

Страница 12: ...ith higher flow rating if head requirement is still satisfied Temperature in the controller is too high If the controller s heat exchanger becomes too hot the controller will reduce the output frequency to the motor to lower the power consumption Make sure there is at least 4 inches of room around the controller for movement of air Avoid direct sunlight Reduce ambient temperature below 104 F 40 C ...

Отзывы: