7 Connection
7.1 Transducers
FLUXUS WD
2018-07-16, UMFLUXUS_WDV1-3EN
56
7.1.4
Connection of the extension cable to the junction box
7.1.4.1
Connection without potential separation (standard)
The connection of the extension cable to the junction box without potential separation ensures that transducer, junction
box and transmitter are on the same potential. The extension cable should always be connected in this manner, especially
if power current cables are nearby the extension cable. If earthing on the same potential cannot be ensured, see section
7.1.4.2.
• Remove the blind plug for the connection of the extension cable.
• Open the cable gland of the extension cable. The compression part remains in the cap nut.
• Push the extension cable through the cap nut and the compression part.
• Prepare the extension cable.
• Shorten the external shield and brush it back over the compression part.
• Screw the gasket ring side of the basic part into the junction box.
• Insert the extension cable into the junction box.
• Fix the cable gland by screwing the cap nut onto the basic part.
• Connect the extension cable to the terminals of the junction box, see Fig. 7.5 and Tab. 7.4.
Tab. 7.3:
Terminal assignment
terminal
connection
V
transducer
(core)
VS
transducer (internal shield)
RS
transducer (inner shield)
R
transducer
(core)
Fig. 7.4:
Connection of the transducer cable with plastic cable jacket and stripped cable ends
1 – cap nut
2 – compression part
3 – basic part
4 – external shield brushed back
Notice!
For good electromagnetic compatibility (EMC), it is important to ensure good electrical contact between the external
shield and the cap nut (and thus the housing).
100
mm
20
mm
10
mm
4
cable gland
1
2
3
Содержание FLUXUS WD
Страница 1: ...FLUXUS WD UMFLUXUS_WDV1 3EN Operating instruction...
Страница 6: ...Table of contents FLUXUS WD 2018 07 16 UMFLUXUS_WDV1 3EN 6...
Страница 150: ...18 Settings 18 9 Key lock FLUXUS WD 2018 07 16 UMFLUXUS_WDV1 3EN 150...
Страница 171: ...Annex FLUXUS WD D Conformity declarations 171 UMFLUXUS_WDV1 3EN 2018 07 16 D Conformity declarations...
Страница 172: ...Annex D Conformity declarations FLUXUS WD 2018 07 16 UMFLUXUS_WDV1 3EN 172...
Страница 173: ......
Страница 174: ......