15 Data logger
FLUXUS WD
15.1 Configuration of the data logger
119
UMFLUXUS_WDV1-3EN, 2018-07-16
Event-based starting time
If it is necessary to start the storing of measured values at
a particular event, select
Event-based
as starting time.
The event is signalized via an input or the event trigger. All
configured inputs and event triggers are displayed in the
scroll list.
• Select the input or the event trigger through which the
event is to be signalized.
• Press ENTER.
The storage rate indicates the interval how often the mea-
sured values are transmitted or stored.
• Select in the scroll list a storage rate intended to store the measured values in case the event is not triggered.
• Press ENTER.
• Select
Off
if no measured values are to be stored, as long as the event is not triggered.
• Press ENTER.
• Select in the scroll list a storage rate intended to store the measured values in case the event is triggered.
• Press ENTER.
• Enter the time interval for the measured values to be stored before reaching the event.
• Press ENTER.
• Enter the time interval for the measured values to be stored if the event is no longer active.
• Press ENTER.
Storage rate FastFood
The
Storage rate FastF
is the storage rate at which the measured values are stored in the FastFood mode.
• Select the menu item
Configuration
in the program branch
Special functions\Data logger
.
• Press ENTER until the menu item
Storage rate FastF
is displayed.
• Enter the value for the
Storage rate FastF
in ms.
• Press ENTER.
Special functions
Data logger
Configuration
Logger channels
Start storing
→
Event-based
Storage rate w/o trig.
Storage rate (trig.)
Buffer time
→П
Buffer time
П→
Special functions\Data logger\
Configuration\Start storing\Event-based
Special functions\Data logger\
Configuration\Start storing\Event-based\
Storage rate w/o trig.
Special functions\Data logger\Configuration\Start storing\Event-based\Storage rate (trig.)
Special functions\Data logger\Configuration\Start storing\Event-based\Buffer time ->
П
Special functions\Data logger\Configuration\Start storing\Event-based\Buffer time
П
->
Special functions\Data logger\Configuration\Storage rate FastF
Содержание FLUXUS WD
Страница 1: ...FLUXUS WD UMFLUXUS_WDV1 3EN Operating instruction...
Страница 6: ...Table of contents FLUXUS WD 2018 07 16 UMFLUXUS_WDV1 3EN 6...
Страница 150: ...18 Settings 18 9 Key lock FLUXUS WD 2018 07 16 UMFLUXUS_WDV1 3EN 150...
Страница 171: ...Annex FLUXUS WD D Conformity declarations 171 UMFLUXUS_WDV1 3EN 2018 07 16 D Conformity declarations...
Страница 172: ...Annex D Conformity declarations FLUXUS WD 2018 07 16 UMFLUXUS_WDV1 3EN 172...
Страница 173: ......
Страница 174: ......