Flash Technology
Revision A - 2/13/2020
53
LIGHTING INSPECTION (LI)
The Lighting Inspection (LI) menu allows the user to test the alarm function of the beacon in all modes, markers
and the photodiode dry contact. The Lighting Inspection can be performed as an automatic function (Automatic LI)
or manually (Manual LI). A description of each LI mode is provided in the following bullet points:
Automatic LI cycles through all test points and logs the results for each. No interaction is required during
an Automatic LI. The previous test results can be reviewed by selecting Display Previous Results in the
Automatic LI menu.
Manual LI requires each test point to be selected. Once the selected function has been tested, the
function must be restored and the next test point selected. This method continues for all lighting
components installed in the system.
Note: Some monitoring systems require additional time between alarm generation and receipt of the alarm.
Manual LI mode is recommended in this instance.
Lighting
Inspection
(LI)
Display Previous
Results
"No Valid Results" Will Be Displayed If A Lighting Inspection Has Not Been Performed.
Automatic LI
Begin Test (1 Button Inspection - Beacons & Markers Tested In
Parallel With No User Interaction.)
Yes /No
Yes Confirm?
Yes Confirm?
Manual LI
Beacon Day Alarm
Alarm/Normal
Beacon White Night Alarm
Alarm/Normal
Beacon Red Night Alarm
Alarm/Normal
Beacon Twilight. Alarm
Alarm/Normal
Marker Alarm
Alarm/Normal
Photodiode Dry Contact Test
Alarm/Normal