Flash Technology
Revision A - 2/13/2020
30
If RF issues persist, install a flat bonding/grounding strap or braid (not wire) from each equipment
enclosure to the tower.
If RF issues persist, (after other work is complete) install copper tape at least 1” wide over the gap on
enclosure or junction box between door and box. Install tape around entire perimeter of the box. Check
that the tape makes a tight metal to metal fit with no gaps.
OTHER INSTALLATION TIPS
To ensure erroneous alarms are not encountered, strip all wires properly to allow solid metal-to-metal
contact on termination points. Make sure all screw electrical connections are hand tight and that plug-in
connectors and terminals are snug and secured on printed circuit boards and terminal blocks.
In each Junction box, point all wire splices up to reduce the chance of moisture damage and connection
degradation.
Ensure all electrical wiring connections meet factory recommended guidelines, NEC codes, and local and
state requirements.
INSTALLATION NOTE
If installation drawings prepared specifically for your site disagree with information provided in this manual, the
site installation drawings should take precedence. Consult any site-specific installation wiring diagram supplied
with your equipment.